2 Short Description
2.1 General
The QAIO 2/2 analog module is used for local extension of the inputs and outputs (I/O) of the Moog
Servo Controller (MSC) control module. The analog levels are identical to the levels of the MSC.
The module is mounted on a DIN top-hat rail and directly connected to the MSC via the internal
extension bus (E-Bus).
2.2 Features
Analog I/O extension module with pulse input.
• 2 analog inputs
• 2 analog outputs
• 1 reference voltage output +10 V
• Pulse input
• Connection via E-Bus
2.3 Outputs/Inputs
• 2 analog inputs, each configurable in the MACS development environment as ±10 V,
±10 mA or 4-20 mA. The inputs are converted in multiplex operation.
• 2 analog outputs, each ±10 V, additionally individually configurable in the MACS software
as ±10 mA, ±50 mA or 4–20 mA with wire fault monitoring
• 1 reference voltage output
The reference voltage source provides a short circuit protected voltage of +10 V.
• 1 pulse input 24 V useable as counter input or frequency measurement input
2.4 Module Status LEDs
On the front, 4 LEDs provide information about the status of important module functions.
2.5 Configuration
The configuration of the analog I/O is carried out per software via the central control configuration
in the Moog Axis Control Software (MACS) development environment.
Either the two analog inputs or the pulse input can be used.
2.6 Actuation
The I/O of the analog extension module is actuated directly from the MSC (not D136X001-001 and
D136E001-001) via the extension bus (E-bus). All input- and output-data are transferred within one
cycle of the E-Bus. Therefore the module is perfect for fast control tasks.
2.7 E-Bus
One MSC can be extended with a maximum of 7 QAIO 2/2 modules. It is not possible to combine it
with QAIO 16/4 on one E-Bus segment.
Module data QAIO 2/2-AV I/O extension module
Order number D137-001-011
Connection to M3000 modules Via E-Bus (10 MHz)
Please note:
• It is not possible to connect the module to an MSC
D136X001-001 or D136E001-001
• Combination with QAIO 16/4 V or QAIO 16/4 A on
one E-Bus segment is not possible
• All QAIO 2/2 A/V modules must be connected next to
the E-Bus master MSC. Further E-Bus modules may
be connected right to the QAIO 2/2 A/V modules.
Connection technique Plug-in terminal strips for screwing or clamping
Mounting Mounting rail NS 35/7.5 pursuant to EN 50022 (DIN top-hat
rail)
4 module status LEDs Module functions and diagnosis
Dimensions, WxHxD 124 x 170 x 85.5 (attachment dimension: W = 113/118.5) mm
4.88 x 6.69 x 3.37 (attachment dimension:
W = 4.45/4.67) inch
Temperature range +5°C (+41°F) to +55°C (+131°F) (operation) and
-25°C (-13°F) to +70°C (+158°F) (storage)
Mean temperature in operation for 24 hrs.: max. +50°C
(+122°F)
Relative air humidity 10 % to 95 % (non-condensing)
Operation height Max. 2000 m (6500 ft); storage/transport max. 3000 m
(9800 ft)
Standards
Operating equipment demands and
examinations
IEC 61131-2
Interference emission / immunity EN 61000-6-4 / EN 61000-6-2, industrial part
Shock / vibration IEC 60068 part 2-27 / IEC 60068 part 2-6
Protection class / protection system III / IP20
Insulation strength IEC 61131-2; test voltage 500 V DC
Energy Supply
Voltage supply of module
electronics
+24 V DC (18-32 V DC) SELV pursuant to DIN EN 60950-1
Current consumption of module
electronics
max. 0.25 A
Potential separation Separate potentials for: module electronics, 24 V energy
supply, pulse input
Internal voltages Internally generated via DC/DC converters
Protection against reverse polarity Yes
Analog Inputs
2 analog inputs 16 Bit; individually configurable in the MACS development
environment as ±10 V, ±10 mA or 4–20 mA;
overvoltage protection up to ±36 V
Analog Outputs
2 analog outputs 16 Bit; each ±10 V, additionally individually configurable in
the MACS development environment as ±10 mA, ±50 mA or
4–20 mA
Overvoltage protection up to ±36 V; short-circuit protected
View of the Module and Terminal Assignment
3.1 View of the Module
Analog Outputs
4.1 Basic Wiring Diagram
4.2 Specifications
Number of analog outputs
2
Analog output type
Voltage output ±10 V nominal
Additionally one current output each:
configurable as: ±10 mA, ±50 mA or 4–20 mA (each nominal)
The analog outputs are configured in the PLC configuration of the
MACS development environment.
Output impedance within nominal signal range
<0.2 W (voltage output)
Approx. 1 MW (current outputs)
Digital resolution
16 bit
Data format in the application program
32 bit floating point
Load impedance range
Voltage output ±10 V: ≥ 1.000 Ω
Current output ±10 mA: ≤ 1.000 Ω
Current output ±50 mA: ≤ 200 Ω