EN 1092-1 PN 16 1.3 kPa abs, 13 mbar abs, 0.2 psia and 13.5 bar
EN 1092-1 PN 40 1.3 kPa abs, 13 mbar abs, 0.2 psia and 33.8 bar
The pressure limit decreases with increasing temperature above 100°F
(38°C), according to ASME B16.5 standards or above 50°C according to
EN 1092-1 standards.
Proof pressure
The transmitter with threaded process connection can be
exposed without leaking to line pressure of up to
• 48 MPa, 480 bar, 6960 psi for standard static version
• up to two times the flange rating for the flange
mounted version.
Meet ANSI/ISA-S 82.03 hydrostatic test requirements.
Temperature limits °C ( °F)
Ambient
is the operating temperature
Models 266DSH Ambient temperature limits
Silicone oil for sensor F to S –40 and 85 °C (–40 and 185 °F)
Silicone oil for sensor A to E –40 and 85 °C (–40 and 185 °F)*
Inert (Galden) for sensor F to S –20 and 85 °C (–4 and 185 °F)
Inert (Galden) for sensor E –10 and 85 °C (14 and 185 °F)
Models 266DSH Ambient temperature limits
LCD integral display –40 and 85 °C (–40 and 185 °F)
LCD display may be affected in visibility below -20°C (-4°F) or above +70°C
(+185°F).
Transmitters with ambient temperature limit of -50°C (-58° F) are available
through special option.
This special option is not compatible with communication protocol option
“7”
IMPORTANT
For Hazardous Atmosphere applications see the
temperature range specified on the certificate/approval
relevant to the aimed type of protection
Process
Models 266DSH Process temperature limits
Silicone oil for sensor F to S –40 and 121 °C (–40 and 250 °F) *
Silicone oil for sensor A to E –25 and 121 °C (–13 and 250 °F) *
Inert (Galden) for sensor F to S –20 and 100 °C (–4 and 212 °F) **
Inert (Galden) for sensor E –10 and 100 °C (14 and 212 °F) **
* 100 °C (212 °F) for application below atmospheric pressure
** 65 °C (150 °F) for application below atmospheric pressure
Models 266DSH Process temperature limits
Viton gasket –20 and 121 °C (–4 and 250 °F)
Storage
Models 266DSH Storage temperature limits
Storage limits –50 and 85 °C (–58 and 185 °F)
LCD integral display –40 and 85 °C (–40 and 185 °F)
* between -40°C (-40° F) and -25°C (-13° F) device response
time might be influenced
Environmental limits
Electromagnetic compatibility (EMC)
Comply with 2014/30/UE to standards EN 61326-1:2013.
For IEC 61508 SIL certified transmitter to
EN 61326-3-1:2008.
For transmitter with option “YE” to NAMUR NE 021 (2004).
Surge immunity level (with surge protector): 4 kV
(according to IEC 61000-4–5 EN 61000–4–5)
Pressure equipment directive (PED)
Comply with 2014/68/UE to standards
ANSI/ISA 61010-1:2012
Category III Module H for PS ≥ than 20 MPa, 200 bar
Sound Engineering Practice (SEP) for PS < 20 MPa, 200 bar
Humidity
Relative humidity: up to 100 %
Condensing, icing: admissible
Vibration resistance
Accelerations up to 2 g at frequency up to 1000 Hz
(according to IEC 60068–2–6)
Shock resistance
Acceleration: 50 g
Duration: 11 ms
(according to IEC 60068–2–27)
Wet and dust-laden atmospheres
The transmitter is dust and sand tight and protected
against immersion effects as defined by IEC 60529 (2001)
to IP 67 (IP 68 on request) or by NEMA Type 4X.
IP65 with Harting Han connector.
Aluminium and AISI housings as barrel version also comply
to IP 66 as defined by IEC 60529 (2001).
IP66W/IP67W/IP68W as standard for Inmetro certification.
...Specification – operative limits
Hazardous atmospheres
(FOR ALL VERSIONS EXCEPT WirelessHART)
With or without integral display
INTRINSIC SAFETY Ex ia:
• ATEX Europe (code E1) approval
II 1 G Ex ia IIC T6...T4 Ga, II 1/2 G Ex ia IIC T6...T4 Ga/Gb,
II 1 D Ex ia IIIC T85 °C Da, II 1/2 D Ex ia IIIC T85 °C Da;
IP66, IP67.
• IECEx (code E8) approval
Ex ia IIC T6...T4 Ga/Gb, Ex ia IIIC T85 °C Da; IP66, IP67.
• NEPSI China (code EY)
Ex ia IIC T4/T5/T6 Ga, Ex ia IIC T4/T5/T6 Ga/Gb,
Ex iaD 20 T85/T100/T135, Ex iaD 20/21 T85/T100/T135.
EXPLOSION PROOF:
• ATEX Europe (code E2) approval
II 1/2 G Ex db IIC T6 Ga/Gb Ta=–50 °C to +75 °C,
II 1/2 D Ex tb IIIC T85 °C Db Ta = –50 °C to +75 °C;
IP66, IP67.
• IECEx (code E9) approval
Ex db IIC T6 Ga/Gb Ta=–50 °C to +75 °C,
Ex tb IIIC T85 °C Db Ta = –50 °C to +75 °C; IP66, IP67.
• NEPSI China (code EZ)
Ex d IIC T6 Gb, Ex tD A21 IP67 T85 °C.
INTRINSIC SAFETY Ex ic:
• ATEX Europe (code E3 ) type examination
II 3 G Ex ic IIC T6...T4 Gc,
II 3 D Ex tc IIIC T85 °C Dc; IP66, IP67.
• IECEx (code ER) type examination
Ex ic IIC T6...T4 Gc, Ex tc IIIC T85 °C Dc; IP66, IP67.
• NEPSI China (code ES) type examination
Ex ic IIC T4~T6 Gc, Ex nA IIC T4~T6 Gc,
Ex tD A22 IP67 T85 °C.
FM Approvals US (code E6) and
FM Approvals Canada (code E4):
• Explosionproof (US): Class I, Division 1,
Groups A, B, C, D; T5
• Explosionproof (Canada): Class I, Division 1,
Groups B, C, D; T5
• Dust-ignitionproof: Class II, Division 1, Groups E, F, G;
Class III, Div. 1; T5
• Flameproof (US): Class I, Zone 1 AEx d IIC T4 Gb
• Flameproof (Canada): Class I, Zone 1 Ex d IIC T4 Gb
• Nonincendive: Class I, Division 2, Groups A, B, C, D T6...T4
• Energy limited (US): Class I, Zone 2 AEx nC IIC T6...T4