Sensor M to S ≤ 100 ms
Sensor F to H ≤ 100 ms*
Total response time for sensor E ≤ 130 ms*, for sensor B ≤ 310 ms*
Total response time includes dead time of 30 ms (for all sensors) with
time constant @ 63.2 % of total step change.
See “Update Rate” for WirelessHART version.
Accuracy rating (Elin)
% of calibrated span, including combined effects of
terminal based linearity, hysteresis and repeatability.
For fieldbus versions SPAN refer to analog input function
block outscale range
Model Sensor for TD
266DSH F to P from 1:1 to 10:1 ± 0.06 %
F to P from 10:1 to 100:1 ± (0.006 x TD) %
E, Q, S from 1:1 to 10:1 ± 0.075 %
Q and S from 10:1 to 100:1 ± (0.0075 x TD) %
E from 10:1 to 30:1 ± (0.0075 x TD) %
B from 1:1 to 10:1 ± 0.10 %
B from 10:1 to 20:1 ± (0.01 x TD) %
A from 1:1 to 4:1 ± 0.10 %
A from 4:1 to 20:1 ± (0.025 x TD) %
266DSH
(option D2)
F to Q from 1:1 to 5:1 ± 0.04 %
F to P from 5:1 to 100:1 ± (0.0105 + 0.0059 x TD) %
Q from 5:1 to 100:1 ± (0.003 + 0.0074 x TD) %
(*) Availability subject to special request and not applicable
for explosionproof and flameproof
Ambient temperature (E∆Tz + E∆Ts)
per 20K change between the limits of –40 °C to +85 °C
(per 36 °F change between the limits of –40 to +185 °F):
Model Sensor for TD up to
266DSH F to Q 10:1 ± (0.03 % URL + 0.045 % span)
E and S 10:1 ± (0.04 % URL + 0.065 % span)
B 10:1 ± (0.06 % URL + 0.10 % span)
A 4:1 ± (0.10 % URL + 0.10 % span)
for an ambient temperature change from –10 °C to +60 °C
(+14 to +140 °F):
Model Sensor for TD up to
266DSH F to Q 10:1 ± (0.055 % URL + 0.08 % span)
E and S 10:1 ± (0.075 % URL + 0.11 % span)
B 10:1 ± (0.11 % URL + 0.18 % span)
A 4:1 ± (0.18 % URL + 0.18 % span)
per 10K change between the limits of –40 °C to –10 °C or
+60° to +85 °C (per 18 °F change between the limits of –40
to +14 °F or +140° to +185 °F):
Model Sensor for TD up to
266DSH F to Q 10:1 ± (0.03 % URL + 0.04 % span)
E and S 10:1 ± (0.04 % URL + 0.055 % span)
B 10:1 ± (0.055 % URL + 0.09 % span)
A 4:1 ± (0.09 % URL + 0.09 % span)
Static pressure (E∆Ps)
(zero errors can be calibrated out at line pressure)
per 0.5 MPa, 5 bar or 72.5 psi (sensor A)
per 2 MPa, 20 bar or 290 psi (sensor B)
per 3.5 MPa, 35 bar or 500 psi (sensor E)
per 7 MPa, 70 bar or 1015 psi (sensor F to S)
Model 266DSH standard static
• zero error: ±0.05 % of URL for sensor F to S
±0.08 % of URL for sensor A, B and E
• span error: ±0.08 % of reading.
Model 266DSH flange mounted
per 2 MPa, 20 bar or 290 psi
• zero error: ±0.05 % of URL for sensor F to P
±0.08 % of URL for sensor E
span error: ±0.08 % of reading.
Supply voltage
Within voltage/load specified limits the total effect is less
than 0.005 % of URL per volt.
Load
Within load/voltage specified limits the total effect is
negligible.
Electromagnetic field
Meets all the requirements of EN 61326 for surge
immunity level (of NAMUR NE 21 on request).
Common mode interference
No effect from 100Vrms @ 50Hz, or 50 V DC
Mounting position
Rotations in the plane of the diaphragm have a negligible
effect. A tilt from the vertical of up to 90° causes a zero
point shift of up to 0.5 kPa (5 mbar, 2 inH2O), which can be
corrected by making an appropriate zero position
adjustment. There is no effect on the measuring span.
In applications where a dynamic inclined installation is
required (e.g. naval applications with maximum vessel
inclination of +/-22.5°), the maximum error can be up to 3
mbar for 266DSH
Such error might be resulting in a deviation from the
standard accuracy with percentual magnitude depending
on the range of the selected device.
In case of non-dynamic inclined installations, this effect
can be eliminated by performing a zero calibration in the
field.
Please contact ABB to assess more in details on the
installation effects
Stability
±0.15 % of URL over a ten years period
(±0.25 % of URL over a ten years period for sensor A or B)
Maximum total performance
For temperature change of 28 °C (50 °F), static pressure
change of 5,1 MPa, 51 bar, 740 psi, for model 266DSH with
accuracy option code D2 (± 0.04 %)
Sensor Span Maximum total performance
F 35 kPa, 350 mbar, 140 inH2O ≤± 0.125 % of calibrated span
H 150 kPa, 1,5 bar, 600 inH2O
M 550 kPa, 5,5 bar, 80 psi
EMperf = √ (E∆Tz + E∆Ts)2
+ E∆Ps 2
+ Elin 2
EMperf = Maximum total performance
E∆Tz = Effect of the ambient temperature on zero
E∆Ts = Effect of the ambient temperature on span
E∆Ps = Effect of the static pressure on span
Elin = Accuracy rating (for terminal-based linearity 0.04 %)
Total performance
similar to DIN 16086
Temperature change in the range from –10 to 60 °C (14 to 140 °F),
static pressure change (266DSH) 10 MPa, 100 bar, 1450 psi
Model Sensor TD Total performance
266DSH std. static, D2 option F to Q 1:1 ≤± 0.16 % of calibrated span
Eperf = √ (E∆Tz + E∆Ts)2
+ E∆Ps 2
+ Elin 2
Eperf = Total Performance
E∆Tz = Effect of the ambient temperature on zero
E∆Ts = Effect of the ambient temperature on span
E∆Ps = Effect of the static pressure on span
Elin = Accuracy rating (for terminal-based linearity 0.04 %