Frequency band: 2.4 GHz DSSS
Update rate: user selectable from 1 sec. to 60 min.
Integrated adjustable omnidirectional antenna
– Output radio frequency: maximum 10 mW (10 dBm) EIRP
– Range: up to 300 m. (328 yds.)
Minimum distance between antenna and person is 0.2 m.
(8 in.)
Telecommunications directive
Every wireless measuring device must be certified in
accordance with the telecommunications directive, in this
case the frequency range. This certification is countryspecific.
European directives
Radio Equipment & Telecommunications Terminal
Equipment Directive 2014/53/UE to standards EN 60950-
1:2013,
EN 62311:2008, EN 301 489-1 V1.9.2, EN 301 489-17 V2.2.1,
EN 300 328 v1.8.1.
In Europe, use of the 2400 - 2483.5 MHz frequency band is
not harmonized. Country-specific regulations must be
observed.
Restrictions for Norway
Operation not permitted within a radius of 20 km around
Ny-Alesund in Svalbard. For more information, see
www.npt.no Norway Posts and Telecommunications site
Extra-european radio frequency licences
USA to FCC Part 15.247:2009;
Canada to IC RSS-210 and ICES-003;
Argentina; United Arab Emirates (UAE); India; Mexico.
PROFIBUS®
PA output
Device type
Pressure transmitter compliant to Profiles 3.0.1
Identification number: 3450 (hex)
Power supply
The transmitter operates from 9 to 32 V DC , polarity
independent, with or without surge protector.
For Ex ia approval power supply must not exceed 17.5 V DC.
Intrinsic safety installation according to FISCO model.
Current consumption
operating (quiescent): 15 mA
fault current limiting: 20 mA max.
Output signal
Physical layer in compliance to IEC 1158–2/EN 61158–2
with transmission to Manchester II modulation, at 31.25
kbit/s.
Output interface
PROFIBUS PA communication according to Profibus
DP50170 Part 2/DIN 19245 part 1–3.
Output update time
25 ms
Data blocks
3 analog input, 1 physical.
Additional blocks
1 Pressure with calibration transducer block
1 Advanced Diagnostics transducer block including
Plugged Input Line Detection
1 Local Display transducer block
Transmitter failure mode
On gross transmitter failure condition, detected by selfdiagnostics, the output signal can be driven to defined
conditions, selectable by the user as safe, last valid or
calculated value.
If electronic failure or short circuit occur the transmitter
consumption is electronically limited at a defined value
(20 mA approx), for safety of the network.
FOUNDATION FieldbusTM output
Device type
LINK MASTER DEVICE
Link Active Scheduler (LAS) capability implemented.
Manufacturer code: 000320hex
Device type code: 0007hex
Power supply
The transmitter operates from 9 to 32 V DC, polarity
independent, with or without surge protector.
For Ex ia approval power supply must not exceed 24 V DC
(FF–816 certification) or 17.5 V DC (FISCO certification).
Current consumption
operating (quiescent): 15 mA
fault current limiting: 20 mA max.
Output signal
Physical layer in compliance to IEC 61158–2/EN 61158–2.
Transmission to Manchester II modulation, at 31.25 kbit/s.
Function blocks/execution period
3 enhanced Analog Input blocks/25 ms max (each)
1 enhanced PID block/40 ms max.
1 standard ARitmetic block/25 ms
1 standard Input Selector block/25 ms
1 standard Control Selector block/25 ms
1 standard Signal Characterization block/25 ms
1 standard Integrator/Totalizer block/25 ms
Additional blocks
1 enhanced Resource block,
1 custom Pressure with calibration transducer block
1 custom Advanced Diagnostics transducer block
including Plugged Input Line Detection
1 custom Local Display transducer block
Number of link objects
35
Number of VCRs
35
Output interface
FOUNDATION fieldbus digital communication protocol to
standard H1, compliant to specification V. 1.7.
Transmitter failure mode
The output signal is “frozen” to the last valid value on
gross transmitter failure condition, detected by selfdiagnostics which also indicate a BAD conditions. If
electronic failure or short circuit occur the transmitter
consumption is electronically limited at a defined value
(20 mA approx), for safety of the network.
Specification – performance
Stated at reference condition to IEC 60770 ambient
temperature of 20 °C (68 °F), relative humidity of 65 %,
atmospheric pressure of 1013 hPa (1013 mbar), mounting
position with vertical diaphragm and zero based range for
transmitter with isolating diaphragms in AISI 316 L ss or
Hastelloy and silicone oil fill and HART digital trim values
equal to 4 mA and to 20 mA span end points, in linear
mode.
Unless otherwise specified, errors are quoted as % of
span.
Some performance referring to the Upper Range Limit are
affected by the actual turndown (TD) as ratio between
Upper Range Limit (URL) and calibrated span.
IT IS RECOMMENDED TO SELECT THE TRANSMITTER
SENSOR CODE PROVIDING THE TURNDOWN VALUE AS
LOWEST AS POSSIBLE TO OPTIMIZE PERFORMANCE
CHARACTERISTICS.
Dynamic performance (according to IEC 61298–1
definition)
Sensors Total response time