• Energy limited (Canada): Class I, Zone 2 Ex nC IIC T6...T4
• Intrinsically safe:Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G T6...T4
Class I, Zone 0 AEx ia IIC T6...T4 (US)
Class I, Zone 0 Ex ia IIC T6...T4 (Canada)
Type 4X, IP66, IP67 for all above markings.
COMBINED FM Approvals US and Canada
• Intrinsically safe (code EA)
COMBINED ATEX, FM and IECEx Approvals (code EN)
Technical Regulations Customs Union EAC (Russia,
Kazakhstan, Belarus), Inmetro (Brazil), Kosha (Korea)
(ONLY FOR WirelessHART VERSION)
With or without integral display
INTRINSIC SAFETY Ex ia:
• ATEX Europe (code E1) approval
II 1 G Ex ia IIC T4 and II 1/2 G Ex ia IIC T4, IP67.
• IECEx (code E8) approval
Ex ia IIC T4
FM Approvals US and FM Approvals Canada:
• Intrinsically safe:Class I, Division 1, Groups A, B, C, D; T4
Class I, Zone 0 AEx ia IIC T4 Gb (US)
Class I, Zone 0 Ex ia IIC T4 Gb (Canada)
IP67 for all above markings.
IMPORTANT
REFER TO CERTIFICATES FOR AMBIENT TEMPERATURE
RANGES RELATED TO THE DIFFERENT TEMPERATURE
CLASSES.
Electrical Characteristics and Options
Optional indicators
Integrated digital display
(code LS; only with HART standard functionality)
Wide screen LCD, 128 x 64 pixel,
52.5 x 27.2 mm (2.06 x 1.07 in.) dot matrix.
Two keys for zero/span or without front
push buttons when ordered with R1
external pushbuttons option
Display may also indicate static pressure,
sensor temperature and diagnostic messages.
Integral display with integral keypad
(code L1; not with HART standard functionality)
Wide screen LCD, 128 x 64 pixel,
52.5 x 27.2 mm (2.06 x 1.07 in.) dot matrix.
Multilanguage. Four keys for configuration
and management of device.
Easy setup for quick commissioning.
User selectable application-specific
visualizations.
Totalized and instantaneous flow indication.
Display may also indicate static pressure, sensor
temperature and diagnostic messages and provides
configuration facilities.
Integral display with Through-The-Glass (TTG) activated
keypad (code L5; not with HART standard functionality)
As above integral display but equipped
with the innovative TTG keypad allowing
the activation of the configuration and
management menus of the device without
the need of removing the transmitter
housing cover. TTG keypad is protected
against accidental activations.
Optional surge protection
Up to 4kV
• voltage 1.2 µs rise time / 50 µs delay time to half value
• current 8 µs rise time / 20 µs delay time to half value
Process diagnostics (PILD)
Plugged impulse line detection (PILD) generates a warning
via communication (HART, PA, FF). The device can be
configured to drive the output to “Alarm current” or set a
status “BAD”.
HART®
digital communication and 4 to 20 mA
output – Standard and Advanced functionality
Device type: 1a06hex (listed with HCF)
Power supply
The transmitter operates from 10.5 to 42 V DC with no
load and is protected against reverse polarity connection
(additional load allows operations over 42 V DC).
For Ex ia and other intrinsically safe approval power
supply must not exceed 30 V DC. Minimum operating
voltage increases to 12.3 V DC with optional surge
protector or to 10.8 V DC with optional conformity to
NAMUR NE 21 (2004).
Ripple
20 mV max on a 250 Ω load as per HART specifications.
Load limitations
4 to 20 mA and HART total loop resistance :
A minimum of 250 Ω is required for HART communication.
Output signal
Two–wire 4 to 20 mA, user-selectable for linear or square
root output, power of 3
/2 or 5
/2 , square root for
bidirectional flow, 22 points linearization table (i.e. for
horizontal or spherical tank level measurement). HART®
communication provides digital process variable
superimposed on 4 to 20 mA signal, with protocol based
on Bell 202 FSK standard.
HART revision 7 is the default HART output.
HART revision 5 is selectable on request.
Output current limits (to NAMUR NE 43 standard)
Overload condition
• Lower limit: 3.8 mA (configurable from 3.8 to 4 mA)
• Upper limit: 20.5 mA (configurable from 20 to 21 mA)
Alarm current
• Lower limit: 3.6 mA (configurable from 3.6 to 4 mA)
• Upper limit: 21 mA (configurable from 20 to 23 mA,
limited to 22 mA for HART Safety; apply for electronics
release 7.1.15 or later)
Factory setting: high alarm current.
...Specification – electrical characteristics and options
IEC 62591 WirelessHART®
output
Device type: 1a06hex (listed with HCF)
Network ID: ABBhex (2747 decimal)
Join keys: 57495245hex (1464422981) 4c455353hex (1279611731)
4649454chex (1179206988) 444b4559hex (1145783641).
Power Supply
1x D-cell size lithium-thionyl chloride battery.
Battery life: 10 years at 32 sec. update time, 8 years at 16
sec. update time or 5 years at 8 sec. update time.
(at reference conditions of 25 ± 2 °C ambient temperature,
data routed from 3 additional devices, LCD off).
THE BATTERY CAN BE REPLACED IN FIELD, ALSO IN
HAZARDOUS CLASSIFIED AREA.
Output signal
IEC 62591 WirelessHART Version 7.5 (IEEE 802.15.4-2006);