or 0.075% as per model/sensor accuracy)
Maximum total performance and Total performance
includes the measuring errors of
• non-linearity including hysteresis and nonreproducibility,
• thermal change of the ambient temperature as regards
the zero signal and the calibrated span,
• effect of static pressure change on the calibrated span,
with transmitter re-zeroed at line pressure.
Specification – physical
(Refer to ordering information sheets for variant availability related to specific model or versions code)
Materials
Process isolating diaphragms (*)
AISI 316 L ss; AISI 316 L ss gold plated; Tantalum;
Hastelloy®
C-276; Hastelloy®
C-276 on AISI 316L ss gasket
seat.
Process flanges, adapters, plugs and drain/vent valves (*)
AISI 316 L ss (1); Hastelloy®
C-276 (2);
Kynar®
(PVDF insert in AISI 316 ss flange).
AISI 316 L ss with flushing connections for high side of
flange mounted version.
Sensor fill fluid
Silicone oil; Inert fill (Galden®
).
Mounting bracket (**)
Zinc plated carbon steel with chrome passivation; AISI 316
ss; AISI 316 L ss.
Gaskets (*)
Viton®
; PTFE.
Sensor housing
AISI 316 L ss.
Bolts and nuts
AISI 316 ss bolts Class A4–80 and nuts Class A4–70
per ISO 3506;
AISI 316 ss bolts and nuts Class A4–50 per ISO 3506, in
compliance with NACE MR0175 Class II (std. static only).
Plated alloy steel bolts per ASTM-A-193-77a grade B7M and
nuts per ASTM A194/A 194 M-90 grade 2HM, in compliance
with NACE MR0175 Class II.
Electronic housing and covers
Aluminium alloy (copper content ≤ 0.3 %) with baked
epoxy finish (colour RAL9002); AISI 316 L ss.
Covers O-ring
Buna N.
Local adjustments (zero, span and write protect)
For Standard HART version:
• Internal for zero and span (on connection board)
• External non-intrusive for zero, span and write protect
in glass filled polyphenylene oxyde, removable (code
R1).
For all other versions:
• External non-intrusive for zero, span and write protect
in glass filled polyphenylene oxyde, removable.
Plates
Transmitter nameplate: AISI 316 ss screwed to the
electronics housing.
Certification plate and optional tag/calibration plate: selfadhesive attached to the electronics housing or AISI 316 ss
fastened to the electronics housing with rivets or screws.
Optional wired-on customer data plate: AISI 316 ss.
Laser printing on metal or thermal printing on selfadhesive.
For AISI 316 L ss housing it is mandatory to select option
I2 or I3 for plates in AISI 316 ss.
Optional wired-on customer data plate can be populated
with customized data (4 lines of 32 characters 4 mm/0.16
in high).
Customized data have to be provided separately: in case
of no data, the wired-on plate will be delivered blank.
Calibration
Standard: at maximum span, zero based range, ambient
temperature and pressure;
Optional: at specified range and ambient conditions.
Device is delivered with a standard 4-point calibration
record
(*) Wetted parts of the transmitter.
(**)U-bolt material: high-strength alloy steel or AISI 316 L ss;
bolts/nuts material: high-strength alloy steel or AISI 316 ss.
(1) Supplied as AISI 316 L or as ASTM A351 Grade CF-3M
(2) Supplied as Hastelloy C-276 or as ASTM A494 alloy
CW-12MW
Optional extras
Mounting brackets (code Bx)
For vertical and horizontal 60mm. (2in) pipes or wall
mounting. (EXCEPT U-BOLT ASSEMBLY WHICH IS NOT
SUPPLIED FOR WALL MOUNTING, PARTS ARE THE SAME
FOR PIPE AND WALL BRACKET OPTIONS, AS PER
RELEVANT MATERIALS).
Display (code Lx)
L1/L5: 4 position (90° steps) user orientable
LS: fixed position
Optional plates (code Ix)
Code I1: AISI 316 ss wired-on plate with laser printed
customized data (4 lines of 32 characters with 4 mm/0.16
in. height).
Code I2: AISI 316 ss plate with laser printed tag (up to 32
characters - long) and calibration details (up to 32
characters: lower and upper range values and engineering
unit) fixed onto transmitter housing.
Code I3: complete set of AISI 316 ss plates (see I1 and I2).
Surge protection (code S2)
Cleaning procedure for oxygen service (code P1)
Test Certificates (test, design, calibration, material
traceability) (codes Cx and Hx)
Tag and manual language (codes Tx and Mx)
Manifold mounting (code A1)
Factory mounting and pressure test of ABB M26
manifolds.
Process connections
on flanges: 1/4 in. – 18 NPT on process axis
on adapters: 1/2 in. – 14 NPT on process axis
centre distance (266DSH): 54 mm. (2.13 in.) on flange;
51, 54 or 57 mm. (2.01, 2.13 or 2.24 in.) as per adapters
fittings
fixing threads: 7/16 in. – 20 UNF at 41.3 mm centre
distance
High pressure side of flange mounted version (*):
2 in. or 3 in., ASME Class 150 or Class 300 RF;
DN 50 or DN 80, PN 16 or PN 40 to EN 1092-1 Type B1
(*) Bolts and nuts, gasket and mating flange supplied by customer.
Electrical connections
Two 1/2 in. – 14 NPT or M20x1.5 threaded conduit entries,
direct on housing. Only M20x1.5 for WirelessHART with
one port used for antenna.
One certified stainless steel plug (supplied loose with