Terminal block
HART version: three terminals for signal/external meter
wiring up to 2.5 mm2
(14 AWG), also connection points for
test and communication purposes.
WirelessHART version: connection points for test and
communication purposes; additional fast connection for
external harvesting unit.
Fieldbus versions: two terminals for signal wiring (bus
connection) up to 2.5 mm2
(14 AWG)
Grounding
Internal and external 6 mm2 (10 AWG) ground termination
points are provided.
Mounting position
Transmitter can be mounted in any position.
Electronics housing may be rotated to any position. A
positive stop prevents over travel.
Mass (without options)
4 kg approx (8.8 lb) for standard static and gauge
versions;
7 to 11 kg approx (16 to 24 lb) for flange mounted version;
add 1.5 kg (3.3 lb) for AISI housing.
Add 650 g (1.5 lb) for packing.
Packing
Carton 27 x 24 x 20 cm approx (11 x 10 x 8 in.);
Carton 35 x 33 x 35 cm approx (14 x 13 x 14 in) for flange
mounted version
Specification – configuration
Transmitter with HART communication
and 4 to 20 mA
Standard configuration
Transmitters are factory calibrated to customer's
specified range. Calibrated range and tag number are
stamped on the tag plate. If a calibration range and tag
data are not specified, the transmitter will be supplied
with the plate left blank and configured as follows:
Engineering Unit kPa
4 mA Zero
20 mA Upper Range Limit (URL)
Output Linear
Damping 1 s
Transmitter failure mode Upscale
Tag Blank (up to 32 alphanumeric
characters - long;
only 8 visible on display - short)
Optional LCD display PV in kPa; output in mA and
in percentage on bargraph
Any or all the above configurable parameters, including
Lower range–value and Upper range-value which must be
the same unit of measure, can be easily changed using the
HART hand–held communicator or by a PC running the
configuration software with DTM for 266 models. The
transmitter database is customized with specified flange
type and material, O–ring and drain/vent materials and
meter code option.
Tag and Calibration
Tag and/or specific calibrated span can be requested
when configuring the device.
Two tag types are available: Short Tag and Long Tag.
See below table for details about tag type applicability /
presence:
Type Max Length On Display On CertificationOn Device Label
Short Tag 8 digits YES YES NO
Long Tag 32 digits NO YES YES
In case no specific indication will be given about the tag
type, data will be considered as Long Tag by default.
In case tag is required on the optional wired-on customer
data plate (optional digits I1, I3) specific indication needs
to be given.
Custom configuration (option N6)
The following data may be specified in addition to the
standard configuration parameters:
Descriptor 16 alphanumeric characters
Message 32 alphanumeric characters
Date Day, month, year
For HART protocol available engineering units of pressure
measure are :
Pa, kPa, MPa
inH2O@4 °C, mmH2O@4 °C, psi
inH2O@68 °F, ftH2O@68 °F, mmH2O@68 °F
inHg, mmHg, Torr
g/cm2
, kg/cm2
, atm
mbar, bar
These and others are available for PROFIBUS and
FOUNDATION Fieldbus.
Transmitter with WirelessHART
communication
Standard configuration
Transmitters are factory calibrated to customer's
specified range. Calibrated range and tag number are
stamped on the tag plate. If a calibration range and tag
data are not specified, the transmitter will be supplied
with the plate left blank and configured as follows:
Engineering Unit kPa
Output scale 0 % Lower Range Limit (LRL)
Output scale 100 % Upper Range Limit (URL)
Output Linear
Update time 16 s
Tag Blank (up to 32 alphanumeric
characters - long;
only 8 visible on display - short)
Optional LCD display PV in kPa; output in
percentage on bargraph
Any or all the above configurable parameters, including
Lower range–value and Upper range-value which must be
the same unit of measure, can be easily changed using the
HART hand–held communicator or by a PC running the
configuration software with DTM for 266 models. The
transmitter database is customized with specified flange
type and material, O–ring and drain/vent materials and
meter code option.
Custom configuration (option N6)
The following data may be specified in addition to the
standard configuration parameters:
Descriptor 16 alphanumeric characters
Message 32 alphanumeric characters
Date Day, month, year
Transmitter with PROFIBUS PA
communication
Standard configuration
Transmitters are factory calibrated to customer’s
specified range. Calibrated range and tag number are
stamped on the tag plate. If a calibration range and tag
data are not specified, the transmitter will be supplied
with the plate left blank and configured as follows:
Measure Profile Pressure
Engineering Unit kPa
Output scale 0 % Lower Range Limit (LRL)
Output scale 100 % Upper Range Limit (URL)
Output Linear
Hi-Hi Limit Upper Range Limit (URL)
Hi Limit Upper Range Limit (URL)
Low Limit Lower Range Limit (LRL)