ED - TYPE EXAMINATION CERTIFICATE
2 Safety Device, Controlling Device or Regulating Device intended for use outside a potentially explosive atmosphere
but required for or contributing to the safe functioning of Equipment and Protective Systems with respect to the
risks of explosion
Directive 2014/34/EU
3 EU - Type Examination Certificate
Number:
Baseefa09ATEX0155 - Issue 6
3.1 In accordance with Article 41 of Directive 2014/34/EU, EC-Type Examination Certificates referring to 94/9/EC that were in
existence prior to the date of application of2014/34/EU (20 April 2016) may be referenced as if they were issued in accordance
with Directive 2014/34/EU. Supplementary Certificates to such EC-Type Examination Certificates, and new issues of such
certificates, may continue to bear the original certificate number issued prior to 20 April 2016.
4
5
6
Product:
Manufacturer:
Address:
MTL4541S, MTL4541T, MTL4544S & MTL4544D Repeater Power Supplies,
4!20mA
Eaton Electric Limited
Great Marlings, Butterfield, Luton, Bedfordshire, LU2 8DL
7 This re-issued certificate extends EC Type Examination Certificate No. Baseefa09ATEX0155 to apply to product designed and
constructed in accordance with the specification set out in the Schedule ofthe said certificate but having any variations specified
in the Schedule attached to this certificate and the documents therein referred to.
8 SGS Baseefa, Notified Body number 1180, in accordance with Article 17 of Directive 2014/34/EU of the European Parliament
and of the Council, dated 26 February 2014, certifies that this product has been found to comply with the Essential Health and
Safety Requirements relating to the design and construction of products intended for use in potentially explosive atmospheres
given in Annex II to the Directive.
The examination and test results are recorded in confidential Report No. See Certificate History
9 Compliance with the Essential Health and Safety Requirements has been assured by compliance with:
EN 60079-0: 2012 + All: 2013 EN 60079-11: 2012
except in respect ofthose requirements listed at item 18 ofthe Schedule.
10 If the sign "X" is placed after the certificate number, it indicates that the product is subject to the Specific Conditions of Use
specified in the schedule to this certificate.
11 This EU - TYPE EXAMINATION CERTIFICATE relates only to the design and construction of the specified product. Further
requirements of the Directive apply to the manufacturing process and supply of this product. These are not covered by this
certificate.
12 The marking ofthe product shall include the following:
® II (1) GD [Ex ia Gal IIC (-20°C Ta +60 0C)
[Ex ia Da] IIIC (-20°C Ta +60°C)
® I (M1) [Ex ia Ma] I (-20°C Ta +60°C)
SGS Baseefa Customer Reference No. 0703 Project File No. 16/0371
This document is issued by the Company subject to its General Conditions for Certification Services accessible at http://www.sgs.com/enrrerms-andConditions.aspx and the Supplementary Terms and Conditions accessible at http://www.sgs.com/SGSBaseefaiTerms-and-Conditions.aspx Attention is drawn to
the limitation of liability, indemnification and jurisdiction issues defined therein. Any holder of this document is advised that information contained herein
reflects the Company's findings at the time of its intervention only and within the limits ofClient's instructions, if any. It does not necessarily indicate that the
equipment may be used in particular industries or circumstances. The Company's sole responsibility is to its Client and this document does not exonerate
parties to a transaction from exercising all their rights and obligations under the transaction documents. This document cannot be reproduced except in full,
schedule included, without prior written approval of the Company. Any unauthorized alteration, forgery or falsification of the content or appearance of this
document is unlawful and offenders may be prosecuted to the fullest extent ofthe law.
SGS Baseefa Limited
Rockhead Business Park, Staden Lane,
Buxton, Derbyshire SK17 9RZ
Telephone +44 (0) 1298766600 Fax +44 (0) 1298766601
e-mail baseefa@sgs.com web site www.sgs.co.uk/baseefa
Registered in England No. 4305578.
Registered address: Rossmore Business Park, Ellesmere Port, Cheshire, CH65 3EN
R S SINCLAIR
TECHNICAL MANAGER
On behalf of SGS Baseefa Limited
Schedule
Issued 26 September 2016
Page 2 of7
14 Certificate Number Baseefa09ATEX0155 - Issue 6
15 Description of Product
The MTL4544S Two Channel Repeater Power Supply, 4/20mA for 'Smart' Transmitters is designed to provide floating
d.c. supplies for energising two 'Smart' 4/20mA Transmitters located in the hazardous area and repeat these currents in the
non-hazardous area, whilst restricting the transfer of energy from the unspecified non-hazardous area apparatus to the
intrinsically safe circuits by means of limitation of current and voltage. The apparatus also allows bi-directional signal
communication between the hazardous and non-hazardous area by the connection of a hand-held communicator (HHC).
The MTL4544S Two Channel Repeater Power Supply, 4/20mA for 'Smart' Transmitters comprises four isolating
transformers that provide galvanic isolation between the hazardous and non-hazardous area circuitry, zener diode chains
and resistors providing voltage and current limitation. The above, together with other electronic components are mounted
on a single printed circuit board (PCB) and housed in a moulded plastic enclosure. Polarised plugs and sockets are
provided for hazardous and non-hazardous area connections. LED indication is fitted to indicate power-on.
The MTL454IS Single Channel Repeater Power Supply, 4/20mA for 'Smart' Transmitters is a depopulated version ofthe
MTL4544S and has only one channel populated.
The MTL4544D Repeater Power Supply, 4/20mA for 2 or 3 Wire Transmitters with two outputs is designed to provide a
floating d.c. supplies for energising a 2 or 3-Wire 4/20mA Transmitter located in the hazardous area and repeat the current
on two channels in the non-hazardous area, whilst restricting the transfer of energy from the unspecified non-hazardous
area apparatus to the intrinsically safe circuits by means of limitation of current and voltage. The apparatus also allows bidirectional signal communication between the hazardous and non-hazardous area by the connection of a hand-held
communicator (HHC). The apparatus uses the same printed circuit board and enclosure as the MTL4544S but is populated
with only one hazardous area transmitter connection and two non-hazardous area outputs fitted.
The MTL454IT Single Channel Repeater Power Supply, 4/20mA for 2 or 3-Wire Transmitters is similar to the
MTL454I S but is fitted with different voltage and current limitation components and therefore has different output
parameters.
MTL4541S, MTL4544S & MTL4544D Input / Output Parameters
Non-hazardous Area Terminals 8, 9, 11, 12, 13 & 14
Urn 253V Lm.S.
The apparatus is designed to operate on non-hazardous area terminals 8, 9, 11, 12, 13 & 14 from a d.c. supply voltage of
up to 35V.
Hazardous Area Terminals 2 W.r.t. 1 (Channel 1)
Or
Hazardous Area Terminals 5 W.r.t. 4 (Channel 2 - MTL4544S model)
28V
93mA
O.65W
o
o
Hazardous Area Terminals 3 W.r.t. 1 (Channel 1)
Or
Hazardous Area Terminals 6 w.r.t. 4 (Channel 2 - MTL4544S model)
1.1V
53mA
15mW
UI
I 1
30V
121mA
C1
L1
o
o
Although the apparatus does not comply with the simple apparatus requirements of Clause 5.7 of EN 60079-11: 2012,
when terminals 3 W.r.t. 1 or terminals 6 W.r.t 4 (MTL4544S model only) are connected in an intrinsically safe circuit the
internal stored energy, voltage and current of the interface will not add more than the values specified in Clause 5.7 of
EN 60079-11: 2012 to the parameters ofthe circuit into which it is connected.
When an external intrinsically safe source is connected to these terminals it should have a source resistance of Uj / Ii and
the capacitance and either the inductance or inductance to resistance ratio (L/R) ofthe hazardous area connections must not
exceed the values detailed in the certificate of the intrinsically safe source. Hazardous area terminals 2 and 5 must not be
used when the source is connected.
Hazardous Area Terminals 2 W.r.t. 3 (Channel 1)
Or
Hazardous Area Terminals 5 W.r.t. 6 (Channel 2 - MTL4544S model)
28V
87mA
0.61W
o
o
Each channel must be considered as a separate intrinsically safe circuit.
Load Parameters
The capacitance and either the inductance or inductance to resistance ratio (L/R) of the hazardous area load connected
must not exceed the following values for either channel:
GROUP CAPACITANCE INDUCTANCE OR LIRRATIO
(J1F) (mH) (J1H/ohm)
Hazardous Area Terminals 2 w.r.t. 1 or 5 W.r.t. 4 (MTL4544S only)
IIC 0.083 4.2 56
IIB* 0.65 12.6 210
IIA 2.15 33.6 444
I 3.76 53.7 668
Hazardous Area Terminals 3 W.r.t. 1 or 6 W.r.t 4 (MTL4544S only)
IIC 100 12.8 2,438
IIB* 1,000 47.8 8,932
IIA 1,000 104.7 18,140
I 1,000 156.2 28,229
Hazardous Area Terminals 2 W.r.t. 3 or 5 W.r.t. 6 (MTL4544S only)
IIC 0.083 4.9 59
lIB* 0.65 20.0 222
IIA 2.15 40.9 469
I 3.76 59.1 710
* Group lIB parameters also applicable for associated apparatus [Ex ia Da] IIIC
Notes:
1) The above load parameters apply when one ofthe two conditions below is given:
- the total Lj ofthe external circuit (excluding the cable) is < 1% ofthe Lovalue or
- the total Ci ofthe external circuit (excluding the cable) is < 1% ofthe Co value.
The above parameters are reduced to 50% when both ofthe two conditions below are given:
- the total Lj ofthe external circuit (excluding the cable) is 1% ofthe Lovalue and
- the total Cj ofthe external circuit (excluding the cable) is 1% ofthe Co value.
The reduced capacitance ofthe external circuit (including cable) shall not be greater than I/-lF for Groups IIB, IIA
& I and 600nF for Group IIC.
MTL4541T Input / Output Parameters
Non-hazardous Area Terminals 8, 9, 11, 13 & 14
Urn 253V r.m.s.
The apparatus is designed to operate on non-hazardous area terminals 8, 9, 11, 13 & 14 from a d.c. supply voltage of up to
35V.
Hazardous Area Terminals 2 W.r.t. 1
22V
167mA
0.92W
o
o
Hazardous Area Terminals 3 W.r.t. 1
1.0V
53mA
14mW
30V
121mA
o
o
Although the apparatus does not comply with the simple apparatus requirements of Clause 5.7 of EN 60079-11: 2012,
when terminals 3 W.r.t. 1 are connected in an intrinsically safe circuit the internal stored energy, voltage and current ofthe
interface will not add more than the values specified in Clause 5.7 of EN 60079-11: 2012 to the parameters of the circuit
into which it is connected.
When an external intrinsically safe source is connected to these terminals it should have a source resistance of Ui / Ii and
the capacitance and either the inductance or inductance to resistance ratio (L/R) ofthe hazardous area connections must not
exceed the values detailed in the certificate of the intrinsically safe source. Hazardous area terminal 2 must not be used
when the source is connected.
Hazardous Area Terminals 2 W.r.t. 3
22V
145mA
0.80W
o
o
Load Parameters
The capacitance and either the inductance or inductance to resistance ratio (L/R) ofthe hazardous area load connected
must not exceed the following values:
GROUP CAPACITANCE INDUCTANCE OR L/RRATIO
(J.lF) (mH) (J.lH/ohm)
Hazardous Area Terminals 2 w.r.t. 1
IIC 0.165 0.91 39
lIB* 1.14 5.5 147
IIA 4.20 10.7 322
I 6.00 16.4 517
* Group IIB parameters also applicable for associated apparatus [Ex ia Da] lIIC
Notes:
1) The above load parameters apply when one ofthe two conditions below is given:
- the total Li ofthe external circuit (excluding the cable) is < 1% ofthe Lo value or
- the total Cj ofthe external circuit (excluding the cable) is < 1% ofthe Co value.
2) The above parameters are reduced to 50% when both ofthe two conditions below are given:
- the total Li ofthe external circuit (excluding the cable) is 1% ofthe Lovalue and
- the total Cj ofthe external circuit (excluding the cable) is 1% ofthe Co value.
The reduced capacitance ofthe external circuit (including cable) shall not be greater than 11lF for Groups IIB, IIA
& I and 600nF for Group IIC.
16 Report Number
GB/BAS/ExTR16.0237/00
17 Specific Conditions of Use
None
18 Essential Health and Safety Requirements
In addition to the Essential Health and Safety Requirements (EHSRs) covered by the standards listed at item 9, the
following are considered relevant to this product, and conformity is demonstrated in the report:
Clause
1.2.7
1.2.8
1.4.1
1.4.2
Subject
Protection against other hazards (LVD type requirements, etc.)
Overloading of equipment (protection relays, etc.)
External effects
Aggressive substances, etc.
Compliance
Manufacturer responsibility
User/Installer responsibility
User/Installer responsibility
User/Installer responsibility
19 Drawings and Documents
New drawings submitted for this issue of certificate:
Number
CI4541-3
Sheet
80f8
Issue
4
Date
7.16
Description
MTL45541S, MTL4541T, MTL4544S, MTL4544D
Certification Label Details - Baseefa
The above drawing is associated and held with IECEx BAS 09.0070 Iss. 6
Current drawings which remain unaffected by this issue:
Certificate No.
Baseefa09ATEX0155/2
Baseefa09ATEXO155/3
Baseefa09ATEX0155/4
Baseefa09ATEXO 155/5
Date
31 January 2011
6 August 2012
4 March 2013
27 January 2014
Comments
i) To permit the alternative fitting of ISMB3EZ** zener diodes in
place of 15MB59**BT3 components currently fitted.
ii) An alternative method of applying the conformal coating to the
PCB fitted 10 the equipment not affecting the original
assessment.
The associated test and assessment is documented in Certification
Report No. GB/BAS/ExTR10.0298/00.
To confirm the current designs of the MTL4541S, MTL4544S &
MTL4544D Repeater Power Supplies, 4/20mA have been reviewed
against the requirements of IEC 60079-0: 2011 and
EN 60079-11: 2012 10 respect of the differences from
EN 60079-0: 2009, EN 60079-11: 2007 and EN 61241-11: 2006 and
none ofthe differences affect the equipment. In accordance with EN
60079-11: 2012, the Group I capacitive load parameters were
corrected and the associated load parameter notes were updated.
The associated assessment is documented in Certification Report
No. GB/BAS/ExTR12.0181/00.
i) To permit minor component changes to the current design to
form the MTL4541T Single Channel Repeater Power Supply,
4/20mA for 2 or 3-Wire Transmitters.
ii) To confirm the current designs ofthe MTL4541S, MTL4541T,
MTL4544S & MTL4544D Repeater Power Supplies, 4/20mA
have been reviewed against the requirements of EN 60079-0:
2012 in respect ofthe differences from IEC 60079-0: 2011 and
none ofthe differences affect the equipment.
The associated assessment is documented in Certification Report
No. GB/BAS/ExTR13.0022/00.
i) To permit minor component changes to the MTL4541 T Single
Channel Repeater Power Supply, 4/20mA for 2 or 3-Wire
Transmitters not affect the original assessment.
ii) To permit minor drawing changes not affecting the original
assessment.
The associated assessment is documented in Certification Report
No. GB/BAS/ExTR14.0019/00.
Baseefa09ATEXO 155 Issue 6 26
2016
September This issue of the certificate incorporates previously issued primary
& supplementary certificates into one certificate and confirms the
current designs meet the requirements of
EN 60079-0: 2012 + All: 2013 & EN 60079-11: 2012.
The certificate also permits the manufacturer's name to be changed
on page 1 ofthe certificate and on the equipment marking.
The associated assessment is documented in Certification Report
No. GB/BAS/ExTR16.0237/00.
For drawings applicable to each issue, see original ofthat issue