YOKOGAWA F3WD64-3N Input-output module
The F3SC21-1N (FA-M3 Value) is a compact programmable controller
consisting of the following modules:
F3BU04-0N base module (with 4 slots)
F3SP05-0P sequence CPU module (with power supply and
memory)
F3WD64-3N I/O module (with 32 inputs and 32 outputs)
The F3SP05-0P double-slot sequence CPU module is installed in the
leftmost slot of the F3BU04-0N 4-slot base module and the
F3WD64-3N I/O module in slot 2. You can install any FA-M3 I/O
modules in slots 3 and 4.
ASSY S926 BK-0
PROGRAMMER
Features
Its compact size greatly reduces installation space.
The sequence CPU module has a 100-240 VAC universal power
supply so that the user doesn't have to worry about the power
supply environment when using the F3SC21-1N.
The high-speed instruction processing capability of the
F3SC21-1N makes it ideal for applications that require high speed
response.
The use of a structured ladder programming language facilitates
programming and maintenance of ladder programs.
The sequence CPU module has the personal computer link
function to communicate with a higher-level computer or display.
The user needs no personal computer link module (F3LC11-1N)
for this purpose.
Programs and data can be saved on an optional ROM pack.
Number of slots 4
Number of free I/O slots 2 (as the sequence CPU and 64-point I/O modules occupy two slots) Base module
(F3BU04-0N)
Weight 140 g
Supply voltage 100-240 V AC, single phase, 50/60 Hz
Supply voltage fluctuation range 85-264 V AC, 50/60 Hz ±3 Hz
Power consumption 35 VA
Inrush current 20 A max. (120 V AC, Ta=25 ºC)
45 A max. (240 V AC, Ta=25 ºC)
Rated output voltage 5 V DC
Rated output current 2.0 A
Insulation resistance 5 MΩ or greater at 500 V DC (between external AC terminals and FG terminal)
Dielectric strength 1500 V AC for 1 minute (between external AC terminals and FG terminal)
FAIL-signal contact output Provided on the front terminal block on the power supply block; contact rating:
24 V DC, 0.3 A (both normally-open and normally-closed terminals available)
Allowable common-mode
voltage of FAIL-signal contact
120 V max. AC or DC
(between FAIL OUTPUT COM terminal and FG terminal)
Leakage current 0.5 mA max.
Allowable momentary power
failure time 20 ms
Power supply block
Noise immunity Immune to noise of up to 1500 Vp-p with 1-s pulse width and 1-ns rise time at 25-60
Hz (as measured with a noise simulator).
Control mode Stored program, cyclic execution
I/O control mode Refreshing method/direct I/O instructions
Programming language Structured ladder language, mnemonic language
Basic instructions 25 types Number of
instructions Application
instructions 227 types
Basic instructions 0.18-0.36 μs/instruction Instruction
processing
speed Application
instructions 0.36 μs min./instruction
Program size 5K steps (can be stored in ROM)
Number of I/O points 2048 points max.
Number of program blocks 32 max.
Sampling trace No
Link to personal computer Yes
Monitoring of scan time 10-200 ms variable
Internal relay I: 4096 points max.
Shared relay —
Extended shared relay —
Link relay L: 2048 points
Special relay M: 2048 points
Timer T: 512 points max. (total of internal and external timers and counters)
Counter C: 512 points max. (total of internal and external timers and counters)
Data register D: 5120 points max.
File register —
Link register W: 2048 points
Special register Z: 512 points
Index register V: 32 points
Shared register —
Devices
Extended shared register —
Sequence
CPU module*1
(F3SP05-0P)
Sequence CPU block
Self-diagnostics Memory error, CPU error, input/output error, syntax check, etc.
Other features
Configuration function (device capacity, data lock-up range at power failure, output
when CPU stops, etc.)
Constant scan function (1 ms to 190 ms)
Debugging functions (forced SET/RESET, online edit, scan operation, etc.)
Error history function (64 records)
Date/clock function (year/month/day/hour/minute/second/day of week)
Program protection functions
ROM programming and data storage
Personal computer link function
Sequence
CPU block
Current consumption 350 mA (5 V DC)*2
External dimensions 58 (W) X 100 (H) X 83.2 (D) mm
Weight 320 g
UL UL508 approved, File No.E188707
(Overvoltage Category*4 II, Pollution Degree*5 2)
CE EMC
Directive
EN 61326-1 Class A, Table 2 (For use in industrial locations)
EN 61326-2-3*6
EN 55011 Class A, Group 1
EN 61000-6-2. EN 61000-3-2. EN 61000-3-3 compliance
Sequence
CPU module*1
(F3SP05-0P)
Common
Compliance
with
safety and
EMC
standards*3
C-Tick EMC
Framework EN 55011 Class A, Group 1 compliance
Input type DC voltage
Number of points 32
Number of points/common 8 points/common
Isolation method Photocoupler isolation
Rated input voltage 24 V DC
Operating voltage 20.4-26.4 V DC
Rated input current 4.1 mA/point (24 V DC)
ON 6.0 V DC min., 3.2 mA min. Operating
voltage/current OFF 5.8 V DC max., 0.9 mA max.
OFF→ON 1.0 ms max. Input
ON→OFF 2.5 ms max.
Input Block
Interrupt No
Output type Transistor contact (sink type)
Number of points 32
Number of points/common 8 points/common
Isolation method Photocoupler isolation
Rated load voltage 24 V DC
Maximum load current 0.1 A/point, 0.4 A/common
OFF→ON 1.0 ms max. Output
Response ON→OFF 1.0 ms max.
Off-time leakage current 0.1 mA max.
Surge protector Zener diode
Output Block
External power supply 24 V DC, 60 mA
Input/output status indicator Lit when on (indicates either input or output status by using the selector switch)
Current consumption 200 mA (5 V DC)
External connection Two 40-pin connectors
Input/Output
module
(F3WD64-3N)
Common
Weight 160 g
*1: When a sequence CPU module is to be used, use the Ladder Diagram Support Program M3. Rev. 2.02 or later.
*2: The total current dissipated by the modules in slots 3 and 4 must be less than 1400 mA.
*3: For details on conforming modules, see “UL-approved, CE marking and C-Tick mark-compliant Modules” (GS 34M06C11-21E) general specification
brochure.
*4: The term Overvoltage Category involves prescriptions on resistance to surge voltage reduction due to lightning and has four categories.
Overvoltage Category II applies to systems with rated voltage of 220/230/240V and applies to electrical appliances, portable devices, etc.
*5: The term Pollution Degree represents the degree of pollution with foreign matter, solid, liquid or gaseous, that may produce a reduction of dielectric
strength or surface resistivity in the operating environment of the equipment. Pollution degree 2 refers to an environment where normally only
non-conductive pollution occurs but occasionally temporary conductivity caused by condensation is to be expected.
*6: EN 61326-2-3 is applicable only to F3CU04-0S and F3CU04-1S