6 - Polarity of the test current pulse. Point = valid BMS traffic, H = A new entry has been made in the history.
17 - Text indicating state of device
18 - Analog output: 0…20 mA or 4…20 mA (selectable)
19 - External test button (N/D contact)
20 - External reset button (N/E contact or wire jumper). When the terminals are open, the device will reset automatically.
21 - STANDBY contacts. When the contacts are closed, the device is forced into standby mode and will not send out a measurement signal.
22 - RS-485 termination (120 Ω) with micro switch S1 and connection BMS bus; S1 = ON = BMS bus terminated, S2 = unassigned
23 - Alarm relay: Alarm 1 (A-ISOMETER®)
24 - Alarm relay: Alarm 2 (A-ISOMETER®)
25 - Alarm relay: System fault and EDS alarm (Adr.:1)

1 - A-ISOMETER® IRDH575
2 - RS-485/BMS protocol
3 - EDS460/EDS461
4 - EDS3090/EDS3091

EDS460 system with IRDH575, EDS460 and measuring current transformers W… in a three-phase AC system 1 - 3AC/3NAC/AC 20…575 V 2 - US  see ordering information, 6 A fuse recommended. 3 - Current transformers, W series 4 - Loads 5 - A-ISOMETER® IRDH575 6 - Ground fault location device EDS460

1 - DC 20 V…308 V
2 - US see ordering information, 6 A fuse recommended.
3 - Current transformers, W…/8000 series
4 - Load PLC
5 - A-ISOMETER® IRDH575
6 - Ground fault location device EDS461 Design of an EDS461 system The above example shows an EDS461 device being fed by a PLC in a DC system. Using an EDS461 device is recommended for PLC inputs due to the sensitivity required.

