DCS; Industrial control system
NameDescriptionContent
NEW CENTER
Current Location:

A-BSLC 500 EtherNet/IP Adapter

From:A-B | Author:LIAO | Time :2025-08-13 | 426 Browse: | 🔊 Click to read aloud ❚❚ | Share:

Important User Information

Read this document and the documents listed in the additional resources section about installation, configuration, and 

operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize

themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.

Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to 

be carried out by suitably trained personnel in accordance with applicable code of practice.

If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be 

impaired.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use 

or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and 

requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for 

actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software 

described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is 

prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

Overview

This chapter provides an introduction to the features and functionalities of the 

1747-AENTR SLC™ 500 EtherNet/IP Adapter. It includes the following sections.

Module Description The 1747-AENTR Adapter enables CompactLogix™ and ControlLogix® 

processors to control SLC™ I/O modules. It is primarily designed to enable 

migration of existing SLC controlled systems to Logix-based systems.

The adapter mainly acts as a gateway between the SLC backplane and 

EtherNet/IP and typically replaces an SLC controller in the 1746 rack. On 

remote SLC racks, it replaces the 1747-ASB module or the ControlNet® adapters 

1747-ACN15 and 1747-ACNR15.

Control of the backplane I/O is accomplished with a CompactLogix or 

ControlLogix controller communicating through an EtherNet/IP router in the 

Logix backplane, across EtherNet/IP, and into the 1747-AENTR gateway. 

As a gateway between the SLC backplane and EtherNet/IP, the 1747-AENTR 

module is a CIP™ server (for both Explicit Messaging and I/O) on the Ethernet 

port, and an SLC host on the 1746 backplane. 

Connections can be made to support 1746 and 1747 analog, digital, and 

specialty I/O modules installed in the backplane.

For the complete list of supported I/O modules, see the table, List of I/O 

Modules Supported by the 1747-AENTR Adapter on page 27.

Topic Page

Module Description 9

Hardware Components 10

The 1747-AENTR in a Logix System 11

Hardware/Software Compatibility 11

Diagnostic Indicators 11

What the Adapter Does 11

Use of the Common Industrial Protocol (CIP) 12

Understand the Producer/Consumer Model 12

Support of Direct Connections 12

IMPORTANT Studio 5000 Logix Designer® application (previously RSLogix 5000®) 

revision 21 and later, and firmware revision 2.001 and later supports:

• multiple chassis, with a maximum number of three chassis;

• a maximum of 30 SLC I/O modules;

• a maximum of 96 Class 1 connections;

• up to 8 Class 3 connections.

The 1747-AENTR in a 

Logix System

In this example, the I/O modules communicate with the controller through the 

1747-AENTR adapter. The controller can produce and consume tags to the I/O. 

Configuration of devices and the network is done through the personal 

computer running the controller and configuration software

Hardware/Software

Compatibility

The adapter and the applications described in this manual is compatible with 

the following firmware revisions and software releases


roduct Firmware Revision/

Software Versions

1747-AENTR 1.001 or later

Logix controller v20 or later

RSLogix 5000 or Logix Designer v20 or later

RSLinx® software v2.59 or later

Diagnostic Indicators The module has the following diagnostic indicators:

• Link 1 and Link 2 status indicator

• Module indicator

• 4-character status display

What the Adapter Does The 1747-AENTR EtherNet/IP adapter performs the following primary tasks:

• Control of real-time I/O data (also known as implicit messaging) – the 

adapter serves as a bridge between I/O modules and the network 

• Support of messaging data for configuration and programming 

information (also known as explicit messaging)

Use of the Common 

Industrial Protocol (CIP)

The adapter uses the Common Industrial Protocol (CIP), the application layer 

protocol specified for EtherNet/IP, the Ethernet Industrial Protocol. It is a 

message-based protocol that implements a relative path to send a message 

from the producing device in a system to the consuming devices. 

The producing device contains the path information that steers the message 

along the proper route to reach its consumers. Since the producing device 

holds this information, other devices along the path simply pass this 

information; they do not store it.

This has the following significant benefits: 

• You do not need to configure routing tables in the bridging modules, 

which greatly simplifies maintenance and module replacement.

• You maintain full control over the route taken by each message, which 

enables you to select alternative paths for the same end device.

Understand the Producer/

Consumer Model

The CIP producer and consumer networking model replaces the old source 

and destination (master and slave) model. The producer and consumer model 

reduces network traffic and increases speed of transmission. In traditional I/O 

systems, controllers poll input modules to obtain their input status. In the CIP 

system, input modules are not polled by a controller. Instead, they produce 

(multicast or unicast) their data periodically or at a cyclic rate.

Unicast is the default for version 20 with multicast as a selectable option. The 

frequency of update depends upon the options chosen during configuration 

and where on the network the input module resides. The input module, 

therefore, is a producer of input data, and the controller is a consumer of the 

data.

The controller also produces data for other controllers to consume. The 

produced and consumed data is accessible by multiple controllers and other 

devices over the EtherNet/IP network. This data exchange conforms to the 

producer and consumer model.

Support of Direct 

Connections

The EtherNet/IP adapter only supports direct connections. A direct connection 

is a real-time data transfer link between a Logix controller and a 1746/1747 I/O 

module through the 1747-AENTR adapter. Direct I/O connections occur at a 

cyclic rate specified by the RPI during configuration

Install Your Adapter

This chapter describes how to install the 1747-AENTR adapter and connect it to 

the EtherNet/IP network.

The following table lists where to find specific information.

Set the Network Address 

Switches

The network address switches are set to 999 and DHCP enabled, by default. 

You can set the network Internet Protocol (IP) address in the following ways: 

• Use the network address switches on the module.

• Use a Dynamic Host Configuration Protocol (DHCP) server, such as 

Rockwell Automation BootP/DHCP.

• Retrieve the IP address from nonvolatile memory.

The adapter reads the network address switches first to determine if the 

switches are set to a valid number. You set the node address by using the 

network address switches. Valid settings range from 001…254.

When the switches are set to a valid number, the adapter’s IP address is 

192.168.1.xxx (where xxx represents the number set on the switches).

The adapter’s subnet mask is 255.255.255.0 and the gateway address is set to 

0.0.0.0. The adapter does not have a host name assigned, or use any Domain 

Name System when using the network address switch settings.

If the switches are set to an invalid number (for example, 000 or a value greater 

than 254 excluding 888), the adapter checks to see if DHCP is enabled. Setting 

the switches to 888 restores default factory settings. 

Topic Page

Set the Network Address Switches 15

Determine Power Requirements 18

Install the Adapter Module in the Chassis 18

Connect Your Adapter to the Ethernet/IP Network through RJ-45 Connection 19

Chapter Summary 2

Enable Web Server in Static IP mode

1. Set the switches to 000 and cycle power to the adapter.

The module LED flashes red and the four-character status display scrolls 

the message “Web Server Enabled”.

2. Set the switches to the desired IP address and cycle power to the adapter.

3. In your web browser, enter the IP address of the adapter.

The web server home page displays.

Disable Web Server in Static IP mode

1. Set the switches to 901 and cycle power to the adapter.

The module LED flashes red and the four-character status display scrolls 

the message “Web Server Disabled”.

2. Set the switches to the desired IP address and cycle power to the adapter.

3. In your web browser, enter the IP address of the adapter.

The web server home page does not display.

Enable Web Server in DHCP mode

Before you begin, verify that you have an active DHCP server on your network.

1. Set the switches to 000 and cycle power to the adapter.

The module LED flashes red and the four-character status display scrolls 

the message “Web Server Enabled”.

2. Set the switches to 999 and cycle power to the adapter.

3. In RSLinx software, check the IP address that was assigned to the 

adapter by the DHCP server and verify the connection.

4. In your web browser, enter the IP address of the adapter.

The web server home page displays.

Disable Web Server in DHCP mode

Before you begin, verify that you have an active DHCP server on your network.

1. Set the switches to 901 and cycle power to the adapter.

The module LED flashes red and the four-character status display scrolls 

the message “Web Server Disabled”.

2. Set the switches to 999 and cycle power to the adapter.

3. In RSLinx software, check the IP address that was assigned to the 

adapter by the DHCP server and verify the connection.

4. In your web browser, enter the IP address of the adapter.

The web server home page does not display.

Enable Web Server in User-set IP mode

1. Set the switches to 000 and cycle power to the adapter.

The module LED flashes red and the four-character status display scrolls 

the message “Web Server Enabled”.

2. Set the switches to 999 and cycle power to the adapter.

3. In RSLinx software, change the Port Configuration setting to “Manual 

IP”, set the desired IP address, and cycle power to the adapter.

4. In your web browser, enter the IP address of the adapter.

The web server home page displays.

Disable Web Server in User-set IP mode

1. Set the switches to 901 and cycle power to the adapter.

The module LED flashes red and the four-character status display scrolls 

the message “Web Server Disabled”.

2. Set the switches to 999 and cycle power to the adapter.

3. In RSLinx software, change the Port Configuration setting to “Manual 

IP”, set the desired IP address, and cycle power to the adapter.

4. In your web browser, enter the IP address of the adapter.

The web server home page does not display.

Determine Power 

Requirements

The Ethernet adapter requires 5V DC with current consumption of 470 mA. 

The power is supplied through backplane from SLC power supply. Remember 

to consider this requirement when planning your system configuration.

Install the Adapter Module 

in the Chassis

After you set the appropriate switch assemblies for your adapter module, 

follow these procedures for installation. 

See the Industrial Controller Wiring and Grounding Guidelines publication 

1770-4.1 for proper grounding and wiring methods to use when installing your 

module. 

1. Remove power from the I/O chassis before inserting (or removing) the 

module.

2. Align the circuit board with the chassis card guide in the left slot.

. Install the module in slot 0 of the chassis by aligning the circuit board 

with the chassis card guide.

The 1747-AENTR module must be installed only in slot 0 (leftmost slot)of 

the chassis. 

 Press firmly and evenly to seat the module in its backplane connectors. 

To remove the module, press the releases at the top and bottom of the 

module and pull it out.

ATTENTION: Do not force the module into the backplane connector. If you 

cannot seat the module with firm pressure, check the alignment. Forcing the 

module can damage the backplane connector or the module.

Connect Your Adapter to the Ethernet/IP Network through RJ-45 Connection Connect your 1747-AENTR adapter module to an Ethernet/IP network as shown in the following example: Wire the RJ-45 connectors as shown. To connect the module to the network, follow these steps: 1. Attach the cables with the RJ-45 connectors to the two Ethernet ports on the bottom of the module. ATTENTION: Do not force the module into the backplane connector. If you cannot seat the module with firm pressure, check the alignment. Forcing the module can damage the backplane connector or the module. WARNING: If you connect or disconnect the communication cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. 1 8 8 1 Signal 1 TxData+ 2 TxData3 Recv Data+ 4 Reserved 5 Reserved 6 Recv Data7 Reserved 8 Reserv

• Module Settings

- Switches

• SLC Backplane Statistics

- I/O Errors

- I/O Scans Completed

- Maximum Scan Time

- Average Scan Time

Use the Network Settings Page

To use the Network Settings page for network related information, follow this 

procedure.

1. Click Network Settings tab at the top of the page or panel on the left.

This opens the Network Settings page. 

2. From the Network Settings page, you can view the following: • Network Interface - Ethernet Address (MAC) - IP Address - Subnet Mask - Default Gateway - Primary Name Server - Secondary Name Server - Default Domain Name - Host Name - Name Resolution • Ethernet Interface Configuration - How the Network Configuration was obtained - Static or Dynamic

• Ethernet Port 1 and 2

- Interface State

- Link Status

- Media Speed

- Duplex

- Autonegotiate Status

Use the Ethernet Statistics Page

To use the Ethernet Statistics page for information about the Ethernet link and 

interface and media counters, use this procedure.

1. Click Ethernet Statistics tab at the top of the page or from the panel on 

the left.

The Ethernet Statistics page open

From the Ethernet Statistics page, you can view the following:

• Ethernet Port 1 and Port 2

- Interface State

- Link Status

- Media Speed

- Duplex

- Autonegotiate Status


  • MOTOROLA TMCP700 W33378F High-Performance Industrial Computing Module
  • MOTOROLA VME Single Board Computer MVME188A
  • MOTOROLA MVME162PA-344 High-Performance Embedded VME Controller
  • MOTOROLA FAB 0340-1049 High-Efficiency Intelligent Embedded Module
  • MOTOROLA 30-W2960B01A High-Performance Industrial Interface Module
  • MOTOROLA MVME712M Transition Module.
  • MOTOROLA MVME5500 Series VME Single-Board
  • MOTOROLA MVME300 High-Reliability GPIB VMEbus Controller
  • MOTOROLA CPCI-6020TM High-Performance CompactPCI Transition Module
  • MOTOROLA MVME162-210 Embedded Controller
  • MOTOROLA MVME162-522A 01-W3960B/61C Embedded Controller
  • MOTOROLA MVME162-512A Embedded Controller
  • MOTOROLA MVME162-512 Embedded Controller
  • MOTOROLA MVME162-220 Embedded Controller
  • MOTOROLA MVME162-13 Embedded Controller
  • MOTOROLA MVME162-10 Embedded Controller
  • MOTOROLA MVME162-012 Embedded Controller
  • MOTOROLA MCP750 CompactPCI Host Slot Processor
  • Phoenix 2320267 QUINT-UPS/ 24DC/ 24DC/10/3.4AH - Uninterruptible power supply
  • Phoenix QUINT4-PS/3AC/24DC/40 - Power supply 2904623
  • Phoenix 2904622 QUINT4-PS/3AC/24DC/20 - Power supply
  • Phoenix 2905012 QUINT-PS/96-110DC/24DC/10/CO - DC/DC converter, protective coating
  • Phoenix 2905011 QUINT-PS/60-72DC/24DC/10/CO - DC/DC converter, protective coating
  • Phoenix 2904600 QUINT4-PS/1AC/24DC/5 - Power supply
  • Phoenix 2904603 QUINT4-PS/1AC/24DC/40 - Power supply
  • Phoenix 2904601 QUINT4-PS/1AC/24DC/10 - Power supply
  • Phoenix 2904602 QUINT4-PS/1AC/24DC/20 - Power supply
  • Phoenix QUINT-PS/60-72DC/24DC/10 - DC/DC converter 2905009
  • Phoenix QUINT-PS/96-110DC/24DC/10 - DC/DC converter 2905010
  • Phoenix QUINT-PS/3AC/24DC/20/CO - Power supply, with protective coating 2320924
  • Phoenix QUINT-PS/1AC/12DC/20 - Power supply 2866721
  • Phoenix 2320908 QUINT-PS/1AC/24DC/ 5/CO - Power supply, with protective coating
  • Phoenix 2866213 QUINT-BUFFER/24DC/20 - Buffer module
  • Phoenix 2866585 QUINT-DIODE/48DC/40 - Redundancy module, with protective coating
  • Phoenix 2320393 QUINT-BUFFER/24DC/24DC/40 - Buffer module
  • Phoenix 2320157 QUINT-DIODE/12-24DC/2X20/1X40 - Redundancy module
  • Phoenix 2907720 QUINT4-DIODE/48DC/2X20/1X40 - Redundancy module
  • Phoenix 2907719 QUINT4-DIODE/12-24DC/2X20/1X40 - Redundancy module
  • Metso A419471 High-Performance Analog Output Module
  • Applied Materials (AMAT) 0190-19092: High-Performance RF Match Controller Board
  • ABB UFC789AE101 3BHE014023R0101 High-Performance AC 800PEC Control Unit
  • GE MIFIIPA55E20HI00 Multilin MIF II Digital Feeder Protection Relay
  • GE DS3815PAHB1A1A Speedtronic Mark IV Processor & Interface Board
  • GE DS3800NB1A Speedtronic Mark IV Power Supply / Regulator Board
  • GE DS3800HIOC Speedtronic Mark IV High-Level Input/Output Board
  • GE DS3800NHVG Speedtronic Mark IV High-Voltage Gate Driver Board
  • ABB 1TGE120011R1010 MC M117 KIT 24VDC CMMB+PTC
  • Woodward 5448-897 Current Differential Protection Relay
  • GE IS220PAOCH1BE Mark VIe Analog I/O Module
  • GE IS220PDOAH1B Mark VIe Discrete Output (PDOA) I/O Pack
  • ABB Feeder Protection and Control REF620E_1G NBFNAAAAAABC6BBN11G
  • ABB MT-91-ARCFPA High-Precision Tension Control Interface Module
  • HIMA PS1000/230010 982200080 high-performance power supply module
  • HIMA H7202 Distribution Fuse Board / Infeed Board
  • HIMA F60DIO24/1601 Safety-Related Controller
  • HIMA F60DO801 Safety-Related Controller
  • HIMA H7201 Line fuse board
  • HIMA HIMatrix ELOP II 892042336 Version V5.6 Build 1501.9810 IV1
  • HIMA HIMatrix SILworX 504110 895400001
  • HIMA HIMatrix SILworX 504111 895210001
  • HIMA OPC DA Server 892042400 Version 3.56.4
  • HIMA OPC Alarm & Event Server (892042420) Version 4.1.3
  • HIMA OPC Alarm & Event Server (892042420) Version 4.0.5
  • Phoenix QUINT-DIODE/12-24DC/2x20/1x40 2320157 Redundancy module
  • Phoenix QUINT-PS/1AC/24DC/40 2866789 Power supply
  • Moore SIY/PRG/4-20MA/10-42DC SIY PC Programmable Signal Isolator and Converter
  • Motorola 01-W3394F-03F Communication Interface Module
  • Motorola AP-4 256 MByte 01-W3839F-07A Communication Module
  • MOTOROLA MVME2432 01-W3394F-03C VME Processor Module
  • MOTOROLA PCE I 01-W3839F-07A VME Processor Module
  • Motorola HPR431 / SYS431 / SYS443 / MFT543 Component Assembly
  • Motorola AP-4 01-W3394F-03G Communication Interface Module
  • Emerson 01-W3878F-02D DeltaV M-Series I/O Module
  • ICS Triplex Trusted T8232 Power Pack Module
  • ALFA LAVAL AAL7000 OXYGEN ANALYSER V0.1
  • Alstom MPM123 Measurement and Protection Module
  • Honeywell 5701 CONTROL SYSTEM
  • KONGSBERG MRU-E-JB1 Host machine
  • Woodward easYgen-3200-1/P1 8440-2049
  • Woodward easYPROTEC-1410-7 8441-1161 8441-1160
  • Woodward MFR300-71M/K45 8444-1111 8444-1112
  • Woodward MFR300-75M 8444-1107 8444-1108 8444-1109
  • Woodward MFR300-71M/K42 8444-1104
  • Woodward MFR300 75M/SU03, Transducer 8444-1093 8444-1094 8444-1095
  • Woodward MFR300-71M 8444-1091 8444-1092
  • Woodward MFR300-15M 8444-1090 8444-1089
  • Woodward MFR300-11M 8444-1071 8440-1089
  • Woodward MFR500-6M/WK0400 + DPC USB 8444-1070
  • Woodward MFR300-15M 8444-1064
  • Woodward SPM-D2-1040B/NYB 8440-2189
  • Woodward SPM-D2-1010B/NYB 8440-2177
  • Woodward SPM-D2-10B/PSY5-FU-D 8440-2170
  • Woodward SPM-D2-1040B/XN analog speed/voltage bias 8440-2190
  • Woodward MFR300-71M 8444-1063
  • SPM-D2-1010B/X analog speed/voltage bias 8440-2168
  • Woodward SPM-D2-1040B/X analog speed/voltage bias 8440-2171
  • Woodward SPM-D2-1010B/N wide range power supply 8440-2174
  • Woodward SPM-D2-1040B/N wide range power supply 8440-2175
  • Woodward SPM-D2-1010B /110VAC sensing 8440-2166
  • Woodward SPM-D2-1040B /400VAC sensing 8440-2164
  • Woodward DTSC-200A 8440-2297
  • Woodward DTSC-200-55B/K38 8440-2155
  • Woodward DTSC-200-51B 8440-1867 8440-1868
  • Woodward 8445-1049 8445-1048 Converter, 1x FO to CAN
  • Woodward easYlite-200 8446-1007 LED Lamp Expansion Module
  • Woodward IKD-OUT-16 16 DO Expansion Card 8440-2306
  • Woodward IKD-IN-16 16 DI Expansion Card 8440-2307
  • Woodward IKD1M 8 DI/8 DO Expansion Card 8440-2116
  • Woodward easYview-07-30 8446-1071
  • Woodward easYFLEX-3400XT-P2 (GAP) 8440-2217
  • Woodward easY-I-3400XT-P1 8440-2293
  • Woodward easY-I-3500XT-P1 8440-2292
  • Woodward MSLC-2XT 8440-2298 Master Synchronizer and Load Control
  • Woodward DSLC-2XT 8440-2299 Digital Synchronizer and Load Control
  • Woodward: GC-3400XT-P1 8440-2267 Group Controller
  • Woodward: LS-612XT-P2 8440-2317
  • Woodward: CONTROL-LS-612XT-P1,8440-2222 Cabinet back mounting
  • Woodward: LS-522-1/P1 8440-2179
  • Woodward: LS-522-5/P1 8440-2151
  • Woodward: LS-512-1/P1 8440-2181
  • Woodward: LS-512-5/P1 8440-2153
  • Woodward: LS-521-1/P1 8440-2178
  • Woodward: CONTROL-LS-521-5/P1 8440-2150
  • Woodward: LS-511-1/P1 8440-2180 Circuit Breaker Control & Protection
  • Woodward: CONTROL-LS-511-5/P1 8440-2152 Circuit Breaker Control & Protection
  • Woodward easYgen-3500XT-P2-LT-RENTAL 8440-2291 Genset Control for
  • Woodward eeasYgen-3500XT-P2-RENTAL 8440-2290
  • Woodward easYgen-3200XT-RENTAL 8440-2285