the load device. This reduces arcing and damage of the output contacts. (High transients can
cause arcing that occurs when switching off an inductive device.)
If you connect a micro controller triac output to control an inductive load, we recommend
that you use varistors to suppress noise. Choose a varistor that is appropriate for the
application. The suppressors we recommend for triac outputs when switching 120V ac
inductive loads are a Harris MOV, part number V175 LA10A, or an Allen-Bradley MOV,
catalog number 599-K04 or 599-KA04. Consult the varistor manufacturer's data sheet when
selecting a varistor for your application.
For inductive dc load devices, a diode is suitable. A 1N4004 diode is acceptable for most
applications. A surge suppressor can also be used. See the table on page 18 for
recommended suppressors.
Surge Suppression for Inductive ac Load Device
Minimizing Electrical Noise on Analog Controllers
Inputs on analog controllers employ digital high-frequency filters that significantly reduce the
effects of electrical noise on input signals. However, because of the variety of applications and
environments where analog controllers are installed and operated, it is impossible to ensure
that all environmental noise will be removed by the input filters.
Several specific steps can be taken to help reduce the effects of environmental noise on
analog signals:
• install the MicroLogix 1000 system in a properly rated (i.e., NEMA) enclosure. Make
sure that the MicroLogix 1000 system is properly grounded.
• use Belden cable #8761 for wiring the analog channels, making sure that the drain
wire and foil shield are properly earth grounded.
• route the Belden cable separate from any ac wiring. Additional noise immunity can be
obtained by routing the cables in grounded conduit.
Grounding Your Analog Cable
Use shielded communication
cable (Belden #8761). The Belden
cable has two signal wires (black
and clear), one drain wire, and a
foil shield. The drain wire and foil
shield must be grounded at one
end of the cable. Do not ground
the drain wire and foil shield at
both ends of the cable.
Specifications
Environmental Specifications (all MicroLogix controllers)
Description Specification
Operating Temperature 0°C to +55°C (+32°F to +131°F) for horizontal mounting
0°C to +40°C (+32°F to +104°F) for vertical mounting(1