DCS; Industrial control system
NameDescriptionContent
NEW CENTER
Current Location:

A-BMicroLogix 1000 Programmable Controllers

From:A-B | Author:LIAO | Time :2025-08-13 | 449 Browse: | 🔊 Click to read aloud ❚❚ | Share:

Important User Information

Because of the variety of uses for the products described in this publication, those responsible 

for the application and use of these products must satisfy themselves that all necessary steps 

have been taken to assure that each application and use meets all performance and safety 

requirements, including any applicable laws, regulations, codes and standards. In no event will 

Allen-Bradley be responsible or liable for indirect or consequential damage resulting from the 

use or application of these products.

Any illustrations, charts, sample programs, and layout examples shown in this publication are 

intended solely for purposes of example. Since there are many variables and requirements 

associated with any particular installation, Allen-Bradley does not assume responsibility or 

liability (to include intellectual property liability) for actual use based upon the examples 

shown in this publication.

Allen-Bradley publication SGI-1.1, Safety Guidelines for the Application, Installation and Maintenance 

of Solid-State Control (available from your local Allen-Bradley office), describes some important 

differences between solid-state equipment and electromechanical devices that should be taken 

into consideration when applying products such as those described in this publication.

Reproduction of the contents of this copyrighted publication, in whole or part, without 

written permission of Rockwell Automation, is prohibited.

Throughout this publication, notes may be used to make you aware of safety considerations. 

The following annotations and their accompanying statements help you to identify a potential 

hazard, avoid a potential hazard, and recognize the consequences of a potential hazard:

WARNING

!

Identifies information about practices or circumstances that can cause 

an explosion in a hazardous environment, which may lead to personal 

injury or death, property damage, or economic loss.

ATTENTION

!

Identifies information about practices or circumstances that can lead 

to personal injury or death, property damage, or economic loss.

IMPORTANT Identifies information that is critical for successful application and 

understanding of the product.

Overview Install your controller using these installation instructions. The only tools you require are a Flat head or Phillips head screwdriver and drill. Catalog Number Detail The catalog number for the controller is composed of the following:

For More Information

Related Publications

If you would like a manual, you can:

• download a free electronic version from the internet: 

http://literature.rockwellautomation.com

• purchase a printed manual by contacting your local Allen-Bradley distributor or 

Rockwell Automation representative

For Refer to this Document Pub. No.

A description on how to use your MicroLogix 1000 

programmable controllers. This manual also contains 

status file data and instruction set information.

MicroLogix 1000 Programmable 

Controllers User Manual

1761-6.3

A procedural manual for technical personnel who use the 

Allen-Bradley Hand-Held Programmer (HHP) to monitor 

and develop control logic programs for the MicroLogix 

1000 controller.

MicroLogix 1000 with Hand-Held 

Programmer (HHP) User Manual

1761-6.2

More information on proper wiring and grounding 

techniques.

Industrial Automation Wiring and 

Grounding Guidelines

1770-4.1

The procedures necessary to install and connect the AIC+ 

and DNI.

Advanced Interface Converter 

(AIC+) and DeviceNet Interface 

(DNI) Installation Instructions

1761-5.11

A more detailed description on how to install and use your 

AIC+ Advanced Interface Converter.

AIC+ Advanced Interface Converter 

User Manual

1761-6.4

A more detailed description on how to install and use your 

DeviceNet Interface.

DeviceNet Interface User Manual 1761-6.5

A more detailed description on how to install and use your 

Ethernet Interface.

Ethernet Interface User Manual 1761-UM006

Safety Considerations

This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous 

locations only (when product or packing is marked).

Use only the following communication cables in Class I, Division 2, Hazardous Locations.

WARNING

!

Explosion Hazard:

• Substitution of components may impair suitability for Class I, 

Division 2.

• Do not replace components or disconnect equipment unless 

power has been switched off and the area is known to be 

non-hazardous.

• Do not connect or disconnect connectors while circuit is live 

unless area is known to be non-hazardous.

• This product must be installed in an enclosure. All cables 

connected to the product must remain in the enclosure or be 

protected by conduit or other means.

• The interior of the enclosure must be accessible only by the use 

of a tool.

• For applicable equipment (for example, relay modules), exposure 

to some chemicals may degrade the sealing properties of the 

materials used in these devices:

– Relays, epoxy

It is recommended that you periodically inspect these devices for 

any degradation of properties and replace the module if 

degradation is found.

Sécurité

Cet équipement est conçu pour être utilisé dans des environnements de Classe 1, Division 2, 

Groupes A, B, C, D ou non dangereux (si indiqué sur le produit ou l'emballage).

N'utiliser que les câbles de communication suivants dans des environnements dangereux de 

Classe 1, Division 2.

AVERTISSEMENT

!

Danger d'explosion :

• La substitution de composants peut rendre cet équipement 

impropre à une utilisation en environnement de Classe 1, 

Division 2.

• Ne pas remplacer de composants ou déconnecter l'équipement 

sans s'être assuré que l'alimentation est coupée et que 

l'environnement est classé non dangereux.

• Ne pas connecter ou déconnecter les connecteurs lorsque le 

circuit est alimenté, à moins que l'environnement ne soit classé 

non dangereux.

• Ce produit doit être installé dans un boîtier. Tous les câbles qui lui 

sont connectés doivent rester dans le boîtier ou être protégés.

Mounting Your Controller Horizontally

The controller should be mounted horizontally within an enclosure using either the DIN rail 

or mounting screw option. Use the mounting template from the front of this document to 

help you space and mount the controller properly.

Using a DIN Rail

To install your controller on the DIN rail:

1. Mount your DIN rail. (Make sure that the 

placement of the controller on the DIN rail 

meets the recommended spacing 

requirements. Refer to the mounting template 

from the back of this document.)

2. Hook the top slot over the DIN rail.

3. While pressing the controller against the rail, 

snap the controller into position.

4. Leave the protective wrap attached until you 

are finished wiring the controller.

Using Mounting Screws

To install your controller using mounting 

screws:

1. Remove the mounting template from the 

back of this document.

2. Secure the template to the mounting 

surface. (Make sure your controller is 

spaced properly.)

3. Drill holes through the template.

4. Remove the mounting template.

5. Mount the controller.

6. Leave the protective wrap attached until you are finished wiring the controller.

Mounting Your Controller Vertically

Your controller can also be mounted vertically within an enclosure using mounting screws or 

a DIN rail. To insure the stability of your controller, we recommend using mounting screws. 

For additional information, refer to the previous section.

To insure the controller's reliability, the following environmental specifications must not be 

exceeded.

Grounding Your Controller

In solid-state control systems, grounding helps limit the effects of noise due to 

electromagnetic interference (EMI). Run the ground connection from the ground screw of 

the controller (third screw from left on output terminal rung) to the ground bus. Use the 

heaviest wire gauge listed for wiring your controller.

You must also provide an acceptable grounding path for each device in your application. For 

more information on proper grounding guidelines, see the Industrial Automation Wiring and 

Grounding Guidelines, (publication 1770-4.1).

ATTENTION

!

All devices connected to the user 24V power supply or to the RS-232 

channel must be referenced to chassis ground or floating. Failure to 

follow this procedure may result in property damage or personal 

injury.

Chassis ground, user 24V ground, and the RS-232 ground are 

internally connected. You must connect the chassis ground terminal 

screw to chassis ground prior to connecting any devices.

On the 1761-L10BWB, -L10BXB, -L16BWB, -L16BBB, -L16NWB, 

-L20BWB-5A, -L32BBB, and -L32BWB controllers, the ground 

associated with the user supplied 24V DC input power and chassis 

ground are internally connected.

Surge Suppression

Inductive load devices such as motor starters and solenoids require the use of some type of 

surge suppression to protect the controller output contacts. Switching inductive loads 

without surge suppression can significantly reduce the life expectancy of relay contacts. By 

adding a suppression device directly across the coil of inductive devices, you prolong the life 

of the output circuits. You also reduce the effects of radiated voltage transients and prevent 

electrical noise from radiating into system wiring and facility.

The following diagram shows an output with a suppression device. We recommend that you 

locate the suppression device as close as possible to the load device.

If you connect a micro controller FET output to an inductive load, we recommend that you 

use an 1N4004 diode for surge suppression, as shown in the illustration on page 17.

Suitable surge suppression methods for inductive load devices include a varistor, an RC 

network, or, for dc loads, a diode. These components must be appropriately rated to suppress 

the switching transient characteristic of the particular inductive device. See the table on 

page 18 for recommended suppressors.

As the following diagram illustrates, these surge suppression circuits connect directly across 

the load device. This reduces arcing and damage of the output contacts. (High transients can 

cause arcing that occurs when switching off an inductive device.)

If you connect a micro controller triac output to control an inductive load, we recommend 

that you use varistors to suppress noise. Choose a varistor that is appropriate for the 

application. The suppressors we recommend for triac outputs when switching 120V ac 

inductive loads are a Harris MOV, part number V175 LA10A, or an Allen-Bradley MOV, 

catalog number 599-K04 or 599-KA04. Consult the varistor manufacturer's data sheet when 

selecting a varistor for your application.

For inductive dc load devices, a diode is suitable. A 1N4004 diode is acceptable for most 

applications. A surge suppressor can also be used. See the table on page 18 for 

recommended suppressors.

Surge Suppression for Inductive ac Load Device

Minimizing Electrical Noise on Analog Controllers

Inputs on analog controllers employ digital high-frequency filters that significantly reduce the 

effects of electrical noise on input signals. However, because of the variety of applications and 

environments where analog controllers are installed and operated, it is impossible to ensure 

that all environmental noise will be removed by the input filters.

Several specific steps can be taken to help reduce the effects of environmental noise on 

analog signals:

• install the MicroLogix 1000 system in a properly rated (i.e., NEMA) enclosure. Make 

sure that the MicroLogix 1000 system is properly grounded.

• use Belden cable #8761 for wiring the analog channels, making sure that the drain 

wire and foil shield are properly earth grounded.

• route the Belden cable separate from any ac wiring. Additional noise immunity can be 

obtained by routing the cables in grounded conduit.

Grounding Your Analog Cable

Use shielded communication 

cable (Belden #8761). The Belden 

cable has two signal wires (black 

and clear), one drain wire, and a 

foil shield. The drain wire and foil 

shield must be grounded at one 

end of the cable. Do not ground 

the drain wire and foil shield at 

both ends of the cable.

Specifications

Environmental Specifications (all MicroLogix controllers)

Description Specification

Operating Temperature 0°C to +55°C (+32°F to +131°F) for horizontal mounting

0°C to +40°C (+32°F to +104°F) for vertical mounting(1


  • MOTOROLA TMCP700 W33378F High-Performance Industrial Computing Module
  • MOTOROLA VME Single Board Computer MVME188A
  • MOTOROLA MVME162PA-344 High-Performance Embedded VME Controller
  • MOTOROLA FAB 0340-1049 High-Efficiency Intelligent Embedded Module
  • MOTOROLA 30-W2960B01A High-Performance Industrial Interface Module
  • MOTOROLA MVME712M Transition Module.
  • MOTOROLA MVME5500 Series VME Single-Board
  • MOTOROLA MVME300 High-Reliability GPIB VMEbus Controller
  • MOTOROLA CPCI-6020TM High-Performance CompactPCI Transition Module
  • MOTOROLA MVME162-210 Embedded Controller
  • MOTOROLA MVME162-522A 01-W3960B/61C Embedded Controller
  • MOTOROLA MVME162-512A Embedded Controller
  • MOTOROLA MVME162-512 Embedded Controller
  • MOTOROLA MVME162-220 Embedded Controller
  • MOTOROLA MVME162-13 Embedded Controller
  • MOTOROLA MVME162-10 Embedded Controller
  • MOTOROLA MVME162-012 Embedded Controller
  • MOTOROLA MCP750 CompactPCI Host Slot Processor
  • Phoenix 2320267 QUINT-UPS/ 24DC/ 24DC/10/3.4AH - Uninterruptible power supply
  • Phoenix QUINT4-PS/3AC/24DC/40 - Power supply 2904623
  • Phoenix 2904622 QUINT4-PS/3AC/24DC/20 - Power supply
  • Phoenix 2905012 QUINT-PS/96-110DC/24DC/10/CO - DC/DC converter, protective coating
  • Phoenix 2905011 QUINT-PS/60-72DC/24DC/10/CO - DC/DC converter, protective coating
  • Phoenix 2904600 QUINT4-PS/1AC/24DC/5 - Power supply
  • Phoenix 2904603 QUINT4-PS/1AC/24DC/40 - Power supply
  • Phoenix 2904601 QUINT4-PS/1AC/24DC/10 - Power supply
  • Phoenix 2904602 QUINT4-PS/1AC/24DC/20 - Power supply
  • Phoenix QUINT-PS/60-72DC/24DC/10 - DC/DC converter 2905009
  • Phoenix QUINT-PS/96-110DC/24DC/10 - DC/DC converter 2905010
  • Phoenix QUINT-PS/3AC/24DC/20/CO - Power supply, with protective coating 2320924
  • Phoenix QUINT-PS/1AC/12DC/20 - Power supply 2866721
  • Phoenix 2320908 QUINT-PS/1AC/24DC/ 5/CO - Power supply, with protective coating
  • Phoenix 2866213 QUINT-BUFFER/24DC/20 - Buffer module
  • Phoenix 2866585 QUINT-DIODE/48DC/40 - Redundancy module, with protective coating
  • Phoenix 2320393 QUINT-BUFFER/24DC/24DC/40 - Buffer module
  • Phoenix 2320157 QUINT-DIODE/12-24DC/2X20/1X40 - Redundancy module
  • Phoenix 2907720 QUINT4-DIODE/48DC/2X20/1X40 - Redundancy module
  • Phoenix 2907719 QUINT4-DIODE/12-24DC/2X20/1X40 - Redundancy module
  • Metso A419471 High-Performance Analog Output Module
  • Applied Materials (AMAT) 0190-19092: High-Performance RF Match Controller Board
  • ABB UFC789AE101 3BHE014023R0101 High-Performance AC 800PEC Control Unit
  • GE MIFIIPA55E20HI00 Multilin MIF II Digital Feeder Protection Relay
  • GE DS3815PAHB1A1A Speedtronic Mark IV Processor & Interface Board
  • GE DS3800NB1A Speedtronic Mark IV Power Supply / Regulator Board
  • GE DS3800HIOC Speedtronic Mark IV High-Level Input/Output Board
  • GE DS3800NHVG Speedtronic Mark IV High-Voltage Gate Driver Board
  • ABB 1TGE120011R1010 MC M117 KIT 24VDC CMMB+PTC
  • Woodward 5448-897 Current Differential Protection Relay
  • GE IS220PAOCH1BE Mark VIe Analog I/O Module
  • GE IS220PDOAH1B Mark VIe Discrete Output (PDOA) I/O Pack
  • ABB Feeder Protection and Control REF620E_1G NBFNAAAAAABC6BBN11G
  • ABB MT-91-ARCFPA High-Precision Tension Control Interface Module
  • HIMA PS1000/230010 982200080 high-performance power supply module
  • HIMA H7202 Distribution Fuse Board / Infeed Board
  • HIMA F60DIO24/1601 Safety-Related Controller
  • HIMA F60DO801 Safety-Related Controller
  • HIMA H7201 Line fuse board
  • HIMA HIMatrix ELOP II 892042336 Version V5.6 Build 1501.9810 IV1
  • HIMA HIMatrix SILworX 504110 895400001
  • HIMA HIMatrix SILworX 504111 895210001
  • HIMA OPC DA Server 892042400 Version 3.56.4
  • HIMA OPC Alarm & Event Server (892042420) Version 4.1.3
  • HIMA OPC Alarm & Event Server (892042420) Version 4.0.5
  • Phoenix QUINT-DIODE/12-24DC/2x20/1x40 2320157 Redundancy module
  • Phoenix QUINT-PS/1AC/24DC/40 2866789 Power supply
  • Moore SIY/PRG/4-20MA/10-42DC SIY PC Programmable Signal Isolator and Converter
  • Motorola 01-W3394F-03F Communication Interface Module
  • Motorola AP-4 256 MByte 01-W3839F-07A Communication Module
  • MOTOROLA MVME2432 01-W3394F-03C VME Processor Module
  • MOTOROLA PCE I 01-W3839F-07A VME Processor Module
  • Motorola HPR431 / SYS431 / SYS443 / MFT543 Component Assembly
  • Motorola AP-4 01-W3394F-03G Communication Interface Module
  • Emerson 01-W3878F-02D DeltaV M-Series I/O Module
  • ICS Triplex Trusted T8232 Power Pack Module
  • ALFA LAVAL AAL7000 OXYGEN ANALYSER V0.1
  • Alstom MPM123 Measurement and Protection Module
  • Honeywell 5701 CONTROL SYSTEM
  • KONGSBERG MRU-E-JB1 Host machine
  • Woodward easYgen-3200-1/P1 8440-2049
  • Woodward easYPROTEC-1410-7 8441-1161 8441-1160
  • Woodward MFR300-71M/K45 8444-1111 8444-1112
  • Woodward MFR300-75M 8444-1107 8444-1108 8444-1109
  • Woodward MFR300-71M/K42 8444-1104
  • Woodward MFR300 75M/SU03, Transducer 8444-1093 8444-1094 8444-1095
  • Woodward MFR300-71M 8444-1091 8444-1092
  • Woodward MFR300-15M 8444-1090 8444-1089
  • Woodward MFR300-11M 8444-1071 8440-1089
  • Woodward MFR500-6M/WK0400 + DPC USB 8444-1070
  • Woodward MFR300-15M 8444-1064
  • Woodward SPM-D2-1040B/NYB 8440-2189
  • Woodward SPM-D2-1010B/NYB 8440-2177
  • Woodward SPM-D2-10B/PSY5-FU-D 8440-2170
  • Woodward SPM-D2-1040B/XN analog speed/voltage bias 8440-2190
  • Woodward MFR300-71M 8444-1063
  • SPM-D2-1010B/X analog speed/voltage bias 8440-2168
  • Woodward SPM-D2-1040B/X analog speed/voltage bias 8440-2171
  • Woodward SPM-D2-1010B/N wide range power supply 8440-2174
  • Woodward SPM-D2-1040B/N wide range power supply 8440-2175
  • Woodward SPM-D2-1010B /110VAC sensing 8440-2166
  • Woodward SPM-D2-1040B /400VAC sensing 8440-2164
  • Woodward DTSC-200A 8440-2297
  • Woodward DTSC-200-55B/K38 8440-2155
  • Woodward DTSC-200-51B 8440-1867 8440-1868
  • Woodward 8445-1049 8445-1048 Converter, 1x FO to CAN
  • Woodward easYlite-200 8446-1007 LED Lamp Expansion Module
  • Woodward IKD-OUT-16 16 DO Expansion Card 8440-2306
  • Woodward IKD-IN-16 16 DI Expansion Card 8440-2307
  • Woodward IKD1M 8 DI/8 DO Expansion Card 8440-2116
  • Woodward easYview-07-30 8446-1071
  • Woodward easYFLEX-3400XT-P2 (GAP) 8440-2217
  • Woodward easY-I-3400XT-P1 8440-2293
  • Woodward easY-I-3500XT-P1 8440-2292
  • Woodward MSLC-2XT 8440-2298 Master Synchronizer and Load Control
  • Woodward DSLC-2XT 8440-2299 Digital Synchronizer and Load Control
  • Woodward: GC-3400XT-P1 8440-2267 Group Controller
  • Woodward: LS-612XT-P2 8440-2317
  • Woodward: CONTROL-LS-612XT-P1,8440-2222 Cabinet back mounting
  • Woodward: LS-522-1/P1 8440-2179
  • Woodward: LS-522-5/P1 8440-2151
  • Woodward: LS-512-1/P1 8440-2181
  • Woodward: LS-512-5/P1 8440-2153
  • Woodward: LS-521-1/P1 8440-2178
  • Woodward: CONTROL-LS-521-5/P1 8440-2150
  • Woodward: LS-511-1/P1 8440-2180 Circuit Breaker Control & Protection
  • Woodward: CONTROL-LS-511-5/P1 8440-2152 Circuit Breaker Control & Protection
  • Woodward easYgen-3500XT-P2-LT-RENTAL 8440-2291 Genset Control for
  • Woodward eeasYgen-3500XT-P2-RENTAL 8440-2290
  • Woodward easYgen-3200XT-RENTAL 8440-2285