DCS; Industrial control system
NameDescriptionContent
NEW CENTER
Current Location:

Woodward 505 Digital Controller For steam turbineses

From:Woodward | Author:yang | Time :2026-01-14 | 371 Browse: | Share:

505 Digital Controller

For steam turbines

8200-1300. 8200-1301. 8200-1302

This chapter provides a brief introduction to other Woodward devices that are easy to integrate with the 505. By understanding the peripheral devices

The functions of the equipment can help you better understand the overall control configuration.

Some of these devices CAN communicate with each other via a digital communication link (Ethernet or CAN, depending on the product)

Connect 505. Through this link, the 505 monitor will allow users to monitor many things from this external device

Signal and status LED. In many cases, these connections allow the 505 to receive the required input signals, for example

Such as KW load signals or synchronization or load distribution bias signals. This eliminates the need to wire these signals to typical ones

The demand for I/O channels, or digital signals can be used as redundant/backup signals for hardwired signals.

Devices supported within the 505 control application will be identified as the "Woodward Link" identifier

All the equipment covered in this section is manufactured or supported by Woodward. Peripheral devices manufactured by other companies are acceptable

Used in conjunction with 505 to perform the following functions, however, they should be confirmed to be compatible with 505 before system operation

And the compatibility of the application.

When DSLC-2 is connected to the 505 controller, it can be used together with a generator to accurately detect three phases

The output power of the RMS generator is synchronized with the actuator generator circuit breaker. Other configurable DSLC-2 feature packs

Including generator load distribution, VAR or power factor control, process control and basic load control.

Woodward 505 digital governor for steam turbines with single or split actuators

This is a "Woodward Link" device.

To enable the Woodward Link feature, select the selection box on the above screen, enter the slave address and DSLC-2 Settings

The prepared IP address. The above figure shows the factory default IP addresses of the DSLC-2 and Ethernet port 3 of the 505.

Once the Ethernet port 3 of the 505 and the network port B of the DSLC-2 are connected with an RJ45 cable

Next, these Settings will allow the two products to communicate automatically.

Once this configuration is completed, DSLC-2 can provide synchronous speed bias signals and synchronous/load distribution bias signals

And the KW output of the generator. The radio buttons on the screen allow users to select the desired functions. Through this chain

The KW valued by the path can be used as an auxiliary KW input signal and is a pre-configured analog input for the KW input

Entry passage.

The following screen shows the available service screens, which can now be accessed for monitoring DSLC-2.

VariStroke-II is a linear electronic-hydraulic actuator designed to provide control valves for operating steam turbines

Or the linear actuator of the valve frame. This actuator can be directly networked with the 505 controller to reduce

Low system complexity and wiring requirements.

To enable the Woodward Link feature, select the selection box on the above screen to enable CAN1 Link and confirm

Use the VariStroke II actuator and then enter the device ID. If an analog (4-20 mA) requires a letter

If the signal is about to be connected to the CAN link and VariStroke, then select the desired function for this signal (recommended)

AI as a backup. Finally, select the steam inlet valve being controlled (for most applications, it is an HP requirement).

This is a "Woodward Link" device.

The MFR 300 is a multi-functional generator protection relay used for detecting and protecting small generators. This is quite a lot.

The functional protection relay integrates all generator protection functions in a common device, reducing the overall system

Installation replicability and cost.

This is a "Woodward Link" device.

The LS-5 series protection relay integrates the synchronization, power detection and protection functions of the generator circuit breaker into one. This assumption

It is designed to function in conjunction with a prime mover controller similar to the 505 to allow for accurate generator operation

Control and provide the required generator protection.

Servo mechanism Position Controller (SPC

The servo mechanism position controller (SPC) can be used to connect the 505 digital controller to the existing valve actuator

Or integrate actions or Woodward actuators that are not directly compatible with 505.

The actuator output of 505 is capable of driving a ratio of 4-20 mA or 20-160 mA (up to 200 mA)

The signal enters an actuator coil. These actuator output signals represent the equivalent of the desired valve position (ratio)

For example, the required signal. If the actuator or servo mechanism assembly of the steam turbine requires a different drive signal,

Or control actions (integrated with invalid Settings), a SPC or equivalent device must be used.

Woodward servo position Controller (SPC) accepts 4-20 mA actuation proportional to the desired valve position

The driving signal of the actuator is activated, and a servo mechanism assembly is correspondingly installed. Woodward SPC is capable

Drive proportional or integrated servo mechanism assemblies with single-pole execution up to 0-400 mA or dual-pole execution of +400 mA

The institution requires signals.

SPC comes with a user-friendly software interface program that allows users to configure the unit to the desired Settings.

Check the complete details of the types of actuators that SPC can connect to in the SPC manual. Below are 505 and

An example of how SPC can be applied to integrated servo mechanism valves. SPC can also handle many feedback devices

Transformation.

The actual power sensor is used to detect the actual power generated by the generator or the actual power flowing through the connecting lines.

Woodward's actual power sensor detects three-phase voltage and three-phase current, and compares the relationship between voltage and current of each phase.

And it generates a 4-20 mA output proportional to the actual power.

Woodward produces two types of actual power sensors. The first type of actual power sensor is designed for

Detect the power flow in only one direction (only 0 to +5 A CT current), and output a ratio of 4 to 20

mA signal. This type of actual power sensor is designed for and should be used to detect the power output of generators

Out. There are many different actual power sensors of this type. Some functions of the optional actual power sensor include

VAR detection, load distribution, 0-1 A CT current detection, and combinations of multiple functions. Please consult Wood.

Get the recommended actual power sensors suitable for your application from a Wards-certified distributor or Woodward factory.

The second type of actual power sensor produced by Woodward is designed to detect through busbar-to-busbar connection lines

Power flow. This actual power sensor (8272-726) detects A CT current ranging from -5 A to +5 A to allow it

Output power flows representing two directions. This actual power sensor provides a 4-20 mA power indication output

Output the signal, with 12 mA representing 0 power current. It is recommended to use this actual power sensor for detection only if it passes

The power current of a connecting line. It is required that this actual power sensor or equivalent equipment detect the input and output power of the power plant

Rate.

Woodward's actual power sensors have terminals labeled "Output" and terminals labeled "KW Read". “KW

The "read" terminal provides a 4-20 mA signal proportional to the actual power, which is used in parallel by the 505 controller

Compatible with it. Therefore, the actual power sensor labeled "Output" is for Woodward's 2301 type control

The device is designed and only compatible with it.

The output of the actual power sensor produced by Woodward has a 2.5Hz low-pass filter (with a delay of 400 ms)

It is used to filter out the high-frequency noise typically generated in the switch-type environment. Therefore, if another one is used

The power converter of this supplier should be verified to have similar filtering criteria before being applied together with 505.

For more information about Woodward's actual power sensors, please refer to Woodward Manual 82018.

Engine Generator Control Package/Load Distribution (EGCP-3 LS)

The Woodward EGCP-3 LS controller is a generator load-based microprocessor designed to work with Wood

Ward speed controllers and automatic voltage regulators are used together in three-phase AC generators. EGCP-3 LS is one

Synchronizer, one load controller, one dead busbar closure system, one VAR/PF controller, one overpass

The process controller, power and energy measurement, and protection relay are integrated into one.

The EGCP-3 LS has a keyboard and two 4-wire display panels on the chassis installed in the front cabinet. The display screen can

It is used to configure and set the controller according to the specific on-site requirements. The display screen can also be used for normal operation services to monitor

Depending on the operation and check the alarm data. All the functions performed on the front panel and all the parameters monitored can be accessed through three

Serial port obtained. These ports can be configured to use Woodward Watch Window software. This is one

An external HMI communicates with Modbus or Servlink DDE software.

The 505 configuration can be configured to use EGCP-3 LS only as a synchronizer, or as a synchronizer and load control

"Device. The EGCP-3 LS provides phase matching or slip frequency and is connected to the unit's automatic voltage regulator in parallel

Match the voltage before connection. It is connected to the 505 through a speed bias signal to control the generator frequency and phase

position. When configured to use EGCP-3 LS only as a synchronizer, 505 must be configured to be configured via analog input

Receive the EGCP-3 speed bias signal and enable this input through contact input or function keys.

When used as a synchronizer and load controller, EGCP-3 LS performs automatic synchronization in accordance with EGCP-3

The operation mode controller load. EGCP-3 LS can be set for basic load, load distribution, and remote load

The setting, or process control mode, depends on the configuration and system conditions.

The load distribution mode of EGCP-3 LS is used to distribute loads to those using EGCP-3 LS and tied to the same isolation busbar

Any other units of the line. When connected in parallel to the power grid, this mode is used together with EGCP-3 MC to allow

The EGCP-3 MC controls the frequency or load of the power plant depending on its operating status.

The remote load setting mode of EGCP-3 LS allows a remote 4-20 mA signal to set the load. EGCP

The process control mode of 3LS allows for the control of any process directly related to the generator load.

After synchronization, it can be obtained by EGCP-3 LS (via 505 synchronization/load input) or by the internal speed of 505 /

The load setting value controls the load of the unit. When configuring the synchronous/load input, the position of the contacts of the power grid circuit breaker is open

Select the unit load control through the internal load setting values of EGCP-3 LS or 505.

Once the generator is synchronized with the EGCP-3 LS software load, the unit to the load setting has an operating mode (base load,

Load distribution and process control have been determined. Upon receiving the instruction, EGCP-3 LS can also perform software unloading on the unit

Negative, simultaneously issue a circuit breaker disconnection command at a set power level.

The PowerSense board receives PT and CT inputs for the generator and busbar to be used within the system controller

The parameters were calculated using EGCP-3. The algorithm used is based on IEEE 1459-2000. For the generator and busbar

The following parameters are provided: Hz, Vac, Amps, W, VA, VAR, PF, phase, voltage modulation, and electricity

Current regulation, negative phase sequence voltage, negative phase sequence current. In the 4-20mA analog output, optional: synchronous oscilloscope,

Generator measurement, main line measurement.

EGCP-3 LS is equipped with the following busbar protection:

Overvoltage/undervoltage (59.27)

Overfrequency/underfrequency (81O, 81U)

Directional (forward/reverse) power (32) *

Negative sequence overcurrent (46

Negative sequence overvoltage (47

Phase overcurrent (51) *

Voltage limiting phase overcurrent (51V) *

Directional VAR

Phase current imbalance (46

The EGCP-3 LS is equipped with the following generator protections:

Overvoltage/undervoltage (59.27)

Overfrequency/underfrequency (81O, 81U)

Directional (input/output) power (32) *

Negative sequence overcurrent (46

Negative sequence overvoltage (47

Phase overcurrent (51) *

Directional VAR

Phase current imbalance (46) *

The rotational speed/frequency is mismatched

Apply 505 in conjunction with redundant I/H or I/P converters

505 can be applied in simplex or redundant actuator systems. For redundant actuator applications, actuators

Channel 1 is configured to lead for HP instructions, and Channel 2 is configured for zero-bias HP2 requirements. this

It will provide the full current from the two actuator drive circuits to the driven device

The selection between the output signals of the converter can be accomplished by using an edge valve or a solenoid delivery valve. Converter status (I/H

Or I/P and pressure feedback signals can be selectively configured into the 505. If necessary, the relay output can be configured

Switch between the outputs of the converter. Manual switching between converters can be achieved through discrete input and Modbus

Or use the PC interface command to start. The automatic switching between converters is carried out by 505 based on drive failure and conversion

The feedback signals of the device status, the output pressure of the converter and the input pressure of the servo mechanism are provided.

Functional details

The use of a dual-actuator configuration can provide redundancy up to the actuator level. A typical redundant I/H (or I/P) system

The milliampere output of the 505 actuator will be converted into the corresponding hydraulic (or pneumatic) pressure of the positioning servo mechanism cylinder

Force. Both converters supply the appropriate pressure to position the steam valve as required by the controller. One of the conversions

One will control the valve position requirements, while the other will be in standby mode. The selection between the output signals of the converter can be made using edges

It can be accomplished by using a valve or a solenoid conveyor valve. The edge valve will select the higher pressure output of the two converters, the solenoid transfer valve

Then select the output of one converter and switch between the two converters based on the relay command from the 505 controller

Change. Either type of valve can be used. Refer to the conveyor valve section for the respective advantages of the two types of valves

Information on strengths/weaknesses.

The converter status (I/H or I/P) and pressure feedback signals should be configured into 505 because of the automatic between converters

Switching is provided and handled by the states of these signals. If necessary, a relay output can be configured (configuration)

It is a relay that serves a control function to switch between the outputs of the converter.

Automatic switching is based on configured I/O (see available I/O options). If a converter is configured, then

If the input is discrete, it is used for fault alarm and automatic switching.

Properly installed valves allow for online converter replacement.

For more information about Woodward's redundant CPC products, refer to Manual 26448 and consult your sales representative

Represent all CPC products.

This chapter is designed to provide users with a concept of the capabilities of the 505 electronic controller and how to apply it in the system

They. Typical applications are all presented in the chart, and their functions are also explained. Each application is equipped

Set and start/run mode annotations to assist application configurators in configuring 505 for their own applications. "Basic"

The device connection is displayed in each application drawing to allow for an understanding of how these devices are connected to the 505 and expanded

Show your abilities.

Speed/Load PID

The speed PID can be controlled and limited

Unit speed/frequency

Unit load

When operating in a solitary network, the speed PID of 505 can be used to control the speed/frequency of the unit and is parallel to the infinite bus

When the power grid is connected in parallel, it can be used to control the load of the unit. The speed PID can be configured to output signals through its actuator

The unit load is detected by the 4-20mA analog input signal from the generator power sensor or the number. When configured to be on

When detecting and controlling the generator load through analog input, what is detected and controlled is the real unit load. By making

The control is carried out by the generator load signal, and any difference in the intake or exhaust pressure of the steam turbine is detected and obtained

Compensation, thereby providing true load control.

The combination of the speed PID and its set value limit allows this PID to limit the unit load. When used as a load limiter for the unit

At that time, it is recommended to configure the 505 to only detect and control the actual generator load. If 505 is applied to soft power

net

Due to the large variations in grid frequency, it is recommended to use auxiliary PID rather than speed PID to limit the load of the unit.

Auxiliary PID

The auxiliary PID of 505 can be configured to control or limit:

Steam turbine inlet pressure

Steam turbine inlet flow rate

Steam turbine exhaust pressure

Steam turbine exhaust flow

Generator power output

Input/output power of power plants or lines

Process temperature

Inlet pressure of the compressor

Inlet flow rate of the compressor

Outlet pressure of the compressor

Outlet flow rate of the compressor

Any process parameters related to the unit load, intake steam pressure/flow rate, exhaust steam pressure/flow rate (depending on the configuration

"Place

The auxiliary PID of 505 can be used as a limiter or controller (enabled and disabled according to instructions). When the configuration is the limit

When making the device, the output of this PID is a low-signal selection compared to the output of the rotational speed PID. This configuration allows for auxiliary PID

Limit the load of the unit based on the detected parameters.

When the auxiliary PID is configured as a controller, it must be accessed through the 505's front panel, contact input, or Modbus

Enable and disable the given instructions. After setting it up in this way, when the auxiliary PID is enabled, the speed PID is disabled

Use and track the output of the auxiliary PID.

To control or limit any of the listed parameters, the 505 must be configured to accept an auxiliary analog input representing the parameter level

Input signal. The exception to this principle is that when controlling or limiting the generator load, the auxiliary PID can be configured to enable

Use and share the KW/ unit load with the speed PID.

Cascade PID

The cascade PID of 505 can be configured for control:

Steam turbine inlet pressure

Steam turbine inlet flow rate

Steam turbine exhaust pressure

Steam turbine exhaust flow

Generator power output

Input/output power of power plants or lines

Process temperature

Inlet pressure of the compressor

Inlet flow rate of the compressor

Outlet pressure of the compressor

Outlet flow rate of the compressor

Any process parameters related to the unit load, intake steam pressure or exhaust steam pressure (depending on the configuration

The cascade PID of 505 can be used to control any of the listed parameters. This PID must pass in front of 505

Enable and disable based on the board, contact input or instructions given by Modbus.

Cascade PID and speed PID cascade are used to change the speed/load of the unit. By directly locating the speed PID

The set value, cascade PID can change the unit speed/load to the controller input parameter. This configuration allows for up to two

Disturbance-free switching is performed between two control modes (speed/load and cascade).

Sample application

The sample applications in this chapter will not demonstrate every possible control configuration or combination. However, these examples can also serve as references

Examine to apply any control combinations or parameters that are not listed or displayed. Apply a control that is desired but not displayed

To set parameters or combinations, refer to one or more typical application configurations that are displayed and similar to the desired control configuration, and then

Replace the displayed control parameters with the desired ones.

To apply a desired but not displayed control parameter or combination, refer to one or more displayed ones that are similar to what you want

The typical application configuration of the control configuration, and then replace the displayed control parameters with the desired control parameters.

Example - To configure 505 to perform a steam turbine exhaust pressure limiting function, use Example 1. "with steam turbine

The application of "pump or compressor outlet pressure control with machine inlet steam pressure limit" is used as a reference. Refer to this example and use exhaust steam

Replace the intake pressure and ignore any specified program Settings to control the outlet pressure of the pump or compressor.

The examples shown in this chapter are summarized as follows:

Example 1: Outlet pressure control of pumps or compressors with inlet steam pressure limits

Example 2: Intake steam pressure control with automatic synchronization and generator power limit

Example 3: Exhaust pressure control with input/output power limits

Example 4: Input/output power control of power plants with DRFD servo mechanism interface

Example 5: Intake steam pressure control with synchronous load distribution in island mode

Example 6: Input/Output power control of power plants with synchronous load distribution in island mode

Example 7: Induction generator control

This is a typical example of a pump or compressor application. With this application, the 505 is configured to normally control the pump/compressor

The outlet pressure is controlled, and the speed control valve position is limited based on the low steam inlet pressure of the steam turbine. Both the auxiliary mode and the cascade mode are used

This sample application. Other applications may or may not use the functions shown in Figure 3-1 and all of the following.

With this application, the pump/compressor outlet pressure is controlled within 505 through a cascade controller. Due to export pressure

To obtain control, which usually affects many other power plant processes, a power plant distributed control system (DCS) can be used

Monitor the process conditions of the power plant and set the positions of cascade setting values. This can be achieved through Modbus communication, discrete elevation and

Lower the instruction or execute it with an analog set value signal.

This application requires a control function restriction type to help maintain the steam intake main pipe when there is a problem with the system main pipe

Pressure. Because the auxiliary PID is the only controller with this capability, it is used according to the low steam turbine intake

The pressure setting is used to detect the steam inlet pressure of the steam turbine and limit the position of the speed control valve.

If a distributed control system of a power plant is used to detect by locating the loads (load distribution) of multiple pumps or compressors

To measure and control a process, this DCS can simulate an input with 505 through a configured remote speed setting value

Connect directly. This enables DCS to control power plants and systems by directly and simultaneously changing the rotational speeds of multiple pumps or compressors

Monitor and compensate under the unified conditions.

All 505 PID controller set values (speed, assist, cascade) can be increased or decreased through configuration

The contacts, configured 4-20mA input, Modbus instructions, or 505 service panel can be changed.


  • Woodward easYgen-2300-1/P1 8440-2122
  • Woodward easYgen-2300-5/P1 8440-2080
  • Woodward -5/P2 8440-1858 Genset Control
  • Woodward -5/P2 8440-1857 Genset Control
  • Woodward 8440-1856 Genset Control
  • Woodward 8440-1855 Genset Control
  • Woodward 8440-2255 Genset Control
  • Woodward 8440-2256 Genset Control
  • ABB AX411/511010/STD Single and dual input analyzers
  • Woodward AX411/511010 Single and dual input analyzers
  • Woodward 8440-2253 Engine Control
  • Woodward easYgen-1400 Manual: 37799. 37889 8440-2251
  • Woodward easYgen-400 Manual: 37884. 37890 8440-2250
  • Woodward High Output DVP, 12KW TB Input/Output 8200-556
  • Woodward High Output DVP, 10KW TB Input/Output 8200-536
  • Woodward High Output DVP, 5KW TB Input/Output 8200-538
  • Woodward 8200-188 723PLUS Digital Speed Control
  • Woodward 8200-186 723PLUS Digital Speed Control
  • A-B 80190-100-01-R Regulator / Logic Control Board
  • A-B 80190-099-01 I/O Interface / Regulator PCB
  • A-B 80190-479-01 Power Logic / Gate Driver Board
  • A-B 80190-480-01-R Power Logic Board / Gate Driver
  • Woodward IP30. TB Input/Output 8200-507
  • Woodward TG-10E, -13E, and –17E Actuator 9904-110
  • Woodward TG to TG611 Conversion Kit 8516-174
  • Woodward TG-17 9904-800 Legacy Mechanical Governors
  • Woodward TG-13 9904-814 Legacy Mechanical Governors
  • Woodward CPC-DX - Dual Redundant Skid model 8918-116
  • Woodward CPC-II - 10 Bar, Class 1, Div. 1 (Zone 1 & 2) 9907-1199
  • Woodward Standard MicroNet+ KitSpeed Combo Module 8262-3183
  • Woodward MicroNet TMR Hardware 8262-1145
  • Woodward Flex500 – Front Panel Mount, LVDC, OCP (8200-1343)
  • Woodward 2300E – Ordinary Locations 8273-1017
  • Woodward Vertex Compressor Control 8200-1370
  • MicroNet Safety Module - Bulkhead Mount 8237-2492 Woodward
  • ProTech TPS - Bulkhead Mount Independent Relays 8237-2602
  • Woodward ProTech-GII - Bulkhead Mount Independent Relays 8237-2594
  • Woodward ProTech-SX - Panel Mount, HV/LV 8237-1242 8237-1243
  • Woodward SPC Servo Position Controller 8200-226 8200-227
  • Woodward Peak200 – Bulkhead Mount, LV 8200-1500
  • Woodward 505HT for Pelton Turbines 8200-1400, 8200-1401
  • Woodward 2301E-HT Hydro (Francis Turbines) P/N 8237-2046
  • Woodward 8273-1013 8273-1014 Digital Electronic Load Sharing
  • Control Panel 9907-2024 Woodward
  • Woodward 8269-1073 17-inch Industrial Touch Panel PC
  • Woodward 5009XT Triple Redundant Turbine Control (8262-1142 & 8262-1143)
  • woodward 5009XT with 2 120 V AC/DC PS 8262-1141
  • woodward RemoteView Software License 8928-5311
  • Woodward 8200-1204 8200-1205 LinkNet-HT Discrete Output Module (16 DOs)
  • Woodward LinkNet-HT RTD Module (8 RTD Inputs) 8200-1200
  • Woodward 8200-1203 LinkNet-HT Analog 4-20 mA Module (8 AI and 2 AO)
  • Woodward 8200-1331 505-DR - HVAC/DC, Ordinary Location
  • Woodward 8200-1330 505-DR - LVDC, Ordinary Location
  • Woodward 8200-1312 505-XT - LVDC, Zone-2 Hazardous Location
  • Woodward 8200-1311 505-XT - HVAC/DC, Ordinary Location
  • Woodward 8200-1310 505XT Digital Turbine Controller
  • ABB REF630 UBFNAAABBBAZANBBXB Feeder Protection and Device
  • UniOP MD03R-02-0042 4-Line HMI Display - Technical Specs | Relianca
  • UniOP MD00R-04-0045 HMI Text Display - Specs & Technical Support | Relianca
  • UniOP MKDR-16-0045 Exor UniOP
  • UniOP CP01R-04-0045 Technical Manual & Specifications | Relianca
  • ABB PPD513 A2A-11165 High-performance controller
  • UniOP eTOP30-0050 operation panel
  • UNIOP CP01F-02-0045 HMI
  • UNIOP eTOP06-0050 A versatile and compact human-machine interface
  • UniOP eTOP10B-0050 Touch Screen Control Panel
  • UniOP CP10G-04 CP10G-04-0045 Interface Module
  • UNIOP MKDR-04-0021 Monochrome LCD (with Contrast Control)
  • UNIOP eTOP03-0046 Monochrome LCD (STN)
  • UNIOP MKDR-16-TA-0045 HMI TOUCH SCREEN
  • UNIOP Operator Interface Display MD02R-04-0042
  • UniOP Display Screen eTOP20C-0050 eTOP20C
  • UniOp eTOP05-0045 eTOP05. eTOP05P Operator Interface Touch Panel
  • UNIOP ETOP11-0050 HMI 5.6Color Operator Interface Touch Panel
  • UniOp eTOP306 Panel
  • UniOP CP04F-04-0045 Human Machine Interface
  • UniOP eTOP308 ETOP308U301 HMI Panel
  • UniOP MD00R-02-0045 Ultra-Compact Industrial Operator Terminal
  • UniOP ePALM10-0061 Handheld Robot Trainer
  • ​UniOP CP05R-04-0045 High-Value Character Operator Terminal
  • UniOP CP01R-04. CP05R-04 and CP01F-02
  • Uniop MD02R-04 - MD02R-04-0045 Industrial PLC Workstation
  • Uniop Cp02r-04-0021 Operating Interface
  • UniOP CP04F-04-1945 Rugged VFD Operator Interface
  • UniOP ECT-16-0045 High-Performance Color Touchscreen HMI
  • UniOP ERT-16-0042 High-Durability Industrial Operator Interface
  • UniOP ePAD04-0046 Compact Industrial Interface
  • UniOP BKDR-16 High-Reliability Monochrome Operator Interface
  • UniOP MKDR-04-004 Control Unit Panel
  • UniOP eTOP515 Series 500 HMI
  • Woodward 8200-1300 High-Precision 505D Steam Turbine Controller
  • ABB PFSK138 3BSE016323R3 High-Performance Digital Board Connection Unit
  • ABB PFSK163 3BSE000435R1 High-Performance Interface Module
  • UniOP ETT-VGA Human-Machine Interface (HMI) terminal
  • ABB PFSK165 3BSE027778R1 VP74201-933CW07 Signal Processing and Communication Unit
  • ABB PFSK164 3BSE021180R1 Tension sensor module and processing board
  • ABB 3BSE006505R1 PFSK 142 Control board
  • ABB PFSK160A 3BSE009514R1 Regulated High-Capacity 24V DC
  • ABB PFSK162 3BSE015088R1 High-performance signal conditioning and processing board
  • ABB PFSK152 3BSE018877R1 Signal concentrator board
  • ALSTOM PIB1201A 3BEC0067 Power Interface Board (PIB)
  • ALSTOM PIB310 3BHB0190 Adapter Module / Printed Circuit Board (PCB)
  • ALSTOM PIB102A 3BEB0180 Communication Card / PCB Module
  • ALSTOM BGTR8HE 24491276A1004 High-Frequency Power Controller / Rack Module
  • ALSTOM AM164 Analog Output / Remote I/O
  • ALSTOM UT150-1 PID temperature controller / process control board
  • ALSTOM AL132 AL132A STO0982E01 Control Motherboard / CPU Card
  • ALSTOM AS111-1 Analog Output (AO) Module
  • ALSTOM AH116-2 Servo Drive / Control Module
  • ALSTOM V4555724-0100 Electromechanical Contactor /Power Switch
  • WATLOW 999D,999A Digital/Analog Dual-Channel Base Unit
  • WATLOW 998D 998A Digital/Analog Dual-Channel Base Unit
  • WATLOW 999D-11FF-AARG Dual-channel digital unit with universal process outputs
  • WATLOW Wattlo 998D-22KK-ARRG is a high-performance dual-channel digital controller.
  • WATLOW 996A Single-loop controller
  • WATLOW 996D-11CC-CUGR Single-loop digital controller
  • WATLOW 996D Single-Channel Digital Temperature/Process Controller
  • WATLOW 997D Digital Dual-Channel Base Unit
  • WATLOW 997A Analog Dual-Channel Variant
  • WATLOW DAC / SDAC,Digital-to-Analog / Serial-to-Analog Modules
  • WATLOW MLS300-OIT Operator Interface Terminal (Keypad/Display),Discontinued
  • WATLOW CIM300 Communication Interface Module (EIA-232/485),Discontinued
  • WATLOW MLS300-CIM Control Interface Module (Comm Bridge),Discontinued
  • WATLOW MLS300-AIM,Analog Input Module (16-channel expansion),Discontinued
  • WATLOW MLS300-PM Processor Module (Central CPU),Discontinued
  • Watlow MLS332 32-Loop Processor Base Unit,Discontinued
  • Watlow MLS316 Multi-loop thermal controller
  • Watlow CLS208 C10000CP high-performance, 8-loop PID temperature controller