DCS Industrial control system
NameDescriptionContent
NEW CENTER
Current Location:

EMERSONDeltaV SISTM Logic Solver

From:EMERSON | Author:LIAO | Time :2025-08-18 | 518 Browse: | 🔊 Click to read aloud ❚❚ | Share:

Control Network: The DeltaV Control Network provides 

communication between the nodes in the DeltaV network. 

Refer to the Installing Your DeltaV Digital Automation 

System manual for complete information on the Control 

Network.

Local Bus: The Local Bus provides communication 

between DeltaV controllers and Logic Solvers and 

between DeltaV controllers and SISnet Repeaters.

Local Peer Bus (SISnet): Logic Solvers communicate 

with other Logic Solvers and with local SISnet Repeaters 

through the carriers over a 2 channel local peer bus. The 

same message is broadcast over both channels. The local 

peer bus must be terminated at both ends. The local peer 

bus is terminated at the left end through the 2-wide 

power/controller carrier and at the right end through a 

terminated 1-wide carrier.

The SISnet Repeaters can be located anywhere on a local 

peer bus – between the DeltaV Controller(s) and the 

terminated 1-wide carrier.

Remote Peer Ring: SISnet Repeaters hosted by one 

DeltaV controller communicate with SISnet Repeaters 

hosted by a different DeltaV controller over a fiber-optic 

remote peer ring. A local SISnet Repeater collects locally 

generated messages that have been designated as global

variables into a single message and sends it to the next 

SISnet Repeater in the ring. Upon receipt of a message, 

the receiving SISnet Repeater broadcasts it on its local 

peer bus (SISnet) and forwards the message to the next 

SISnet Repeater in the ring. A global message is 

forwarded around the ring once. The primary SISnet 

Repeaters form one fiber-optic ring and the secondary 

form a separate, independent ring.

Carrier extender cables and local peer bus extender 

cables connecting a DeltaV controller and 8-wide carrier 

with standard DeltaV I/O and DeltaV SIS Logic Solvers to 

a second 8-wide carrier (hosted by the same controller) 

are installed with Logic Solvers, SISnet Repeaters, and a 

terminated 1-wide carrier. Logic Solver messages are 

communicated to a remote DeltaV SIS (hosted by a 

separate controller) through fiber-optic cables.

DeltaV SIS Product Data Sheet

May 2013 – Page 5 DeltaV SIS Logic Solver

Unique Redundancy Methodology

Introduction to Redundancy

Unlike other SIS Logic Solvers, the SLS 1508 is rated 

suitable for use in SIL 3 applications in simplex mode. 

Redundant SLS 1508 Logic Solvers run in parallel at all 

times. Both read the inputs from the I/O terminals, both 

execute the logic and both drive the outputs at the I/O 

terminals. There is no concept of primary and backup or 

master and slave, which is unlike any other SIS. The only 

difference between the two is that one communicates with 

both the engineering and operator workstations and the 

dedicated safety network (SISnet); this is the one with the 

Active light on the bezel. The other (Standby) is 

communicating only on the SISnet.

In the event that a failure is detected in one of the SLS 

1508 Logic Solvers, it automatically goes to a failed state. 

In this condition all its output channels are de-energized; 

this has no impact on the other Logic Solver or the 

physical outputs because the other Logic Solver continues 

to read inputs, execute logic and drive outputs. The 

transition from redundant to simplex mode is therefore 

completely bumpless.

Redundancy

The redundant SLS 1508 Logic Solver modules are 

connected to the field at the redundant terminal block. No 

control strategy configuration is required to take 

advantage of SLS 1508 Logic Solver redundancy, as the 

system’s auto-sense capability automatically recognizes 

the redundant pair of Logic Solvers.

An integrity error alarm in a redundant Logic Solver pair 

will notify the operator of a failure. Both Logic Solvers in a 

redundant pair are monitored for integrity alarms at all 

times.

Events that can cause integrity alarms include:

 Hardware failure within a Logic Solver

 Communications failure between a Logic Solver and 

the SISnet

 Communications failure between a redundant pair of 

Logic Solvers

 Communications failure between a Logic Solver and 

an DeltaV Controller

 Removal of a Logic Solver from the carrier

The health and status of both Logic Solvers and their 

channels are available in the diagnostics explorer.

When one of a redundant pair of SLS 1508 Logic Solvers 

is removed online there is no disturbance to the process. 

When the missing Logic Solver is replaced with another 

Logic Solver, the new Logic Solver completes its power-up 

self-tests before the active Logic Solver cross-loads the 

current database. In safe areas, failed Logic Solvers can 

be replaced under power. In hazardous areas, appropriate 

installation procedures must be followed.

Automatic proof testing can be selected on a redundant 

pair of Logic Solvers. The desired proof-test interval is set 

in the configuration and the Logic Solvers perform the 

  • SEL SEL-T35 Time-Domain Power Monitor
  • SEL SEL-735 Power Quality and Revenue Meter
  • SEL SEL-TWFL Dual Traveling-Wave Fault Locator and 12-Channel MHz Recorder
  • SEL SEL-5035 acSELerator Diagram Builder Software
  • SEL SEL-5033 acSELerator RTAC Software
  • SEL SEL-2411P Pump Automation Controller
  • SEL SEL-2411 Programmable Automation Controller
  • SEL SEL-3560 Real-Time Automation Controller (RTAC)
  • SEL SEL-3555 Real-Time Automation Controller (RTAC)
  • SEL SEL-3350 Computing Platform
  • SEL SEL-3530-4 Real-Time Automation Controller (RTAC)
  • SEL SEL-3505/3505-3 Real-Time Automation Controller (RTAC)
  • SEL Real-Time Automation Controller (RTAC)
  • SEL SEL-2414 Transformer Automation Controller (TAC)
  • SEL SEL-734B Advanced Monitoring and Control System
  • SEL SEL-734W and LINAM WCS
  • SEL SEL-2431 Voltage Regulator Control
  • SEL SEL-5601-2 Synchrowave Event Software
  • SEL SEL-5032 acSELerator Architect Software
  • SEL SEL-5030 acSELerator QuickSet Software
  • SEL SEL-751A Feeder Protection Relay
  • SEL SEL-2440 DPAC Discrete Programmable Automation Controller
  • SEL SEL-2240 Axion
  • SEL SEL-401 Protection, Automation, and Control Merging Unit
  • SEL SEL-TMU TiDL Merging Unit
  • SEL SEL-700BT Motor Bus Transfer Relay
  • SEL SEL-849 Motor Management Relay
  • SEL SEL-3790 Low-Voltage Divider Module
  • SEL SEL-710-5 Motor Protection Relay
  • SEL SEL-487V Capacitor Bank Protection, Automation, and Control System
  • SEL SEL-351RS Kestrel Single-Phase Recloser Control
  • SEL SEL-651RA Recloser Control
  • SEL SEL-651R Advanced Recloser Control
  • SEL SEL-551C Overcurrent/Reclosing Relay
  • SEL SEL-351S Protection System
  • SEL SEL-851 Feeder Protection Relay
  • SEL SEL-451 Protection, Automation, and Bay Control System
  • SEL SEL-751 Feeder Protection Relay
  • SEL SEL-311C Transmission Protection System
  • SEL SEL-387L Line Current Differential Relay
  • SEL SEL-311L Line Current Differential Protection and Automation System
  • SEL SEL-787L Line Current Differential Relay
  • SEL SEL-421 Protection, Automation, and Control System
  • SEL SEL-9L Line Relay
  • SEL SEL-411L Advanced Line Differential Protection, Automation, and Control System
  • SEL SEL-587Z High-Impedance Differential Relay
  • SEL SEL-7251 Electromechanical Direct-Replacement Assemblies
  • SEL SEL-787Z High-Impedance Differential Relay and SEL-HZM High-Impedance Module
  • SEL SEL-487B Bus Differential and Breaker Failure Relay
  • SEL SEL-387 Current Differential and Overcurrent Relay
  • SEL SEL-387A Current Differential and Overcurrent Relay
  • SEL SEL-2600 RTD Module
  • SEL SEL-387E Current Differential and Voltage Relay
  • SEL SEL-787-2/-3/-4 Transformer Protection Relay
  • SEL SEL-487E Transformer Protection Relay
  • SEL SEL-2664S Stator Ground Protection Relay
  • SEL SEL-300G Generator Relay
  • SEL SEL-700G Generator Protection Relay
  • SEL SEL-700G Generator Protection Relay
  • SEL SEL-400G Advanced Generator Protection System
  • SEL SEL-T400L Time-Domain Line Protection
  • SEL SEL-T401L Ultra-High-Speed Line Relay
  • ADLINK Multi-Function DAQ PCI-9222/9223
  • ADLINK PICMG Single Board Computers NuPRO-A40H
  • ADLINK HSL-4XMO HSL-4XMO-TB-D103 HSL-4XMO-CD-N-006
  • ADLINK industrial computer motherboard NuPRO-965DV
  • AADLINK PCI-7442 switch card Digital I/O
  • ADLINK PCI-7260 Digital I/O
  • ADLINK PICMG Single Board Computers NuPRO-852
  • ADlink 6U CompactPCI 2.0 Blades cPCI-6840
  • Adlink  PICMG Single Board Computers  NuPRO-935A
  • ADLINK ADLINK NuPRO-841 REV:1.0 PICMG Single Board Computers
  • ADLINK PCI-8254 / PCI-8258 DSP-based 4/8-axis Advanced Motion Controllers
  • ADLINK NUPRO-780 PICMG Single Board Computers
  • ADLINK USB-7230/7250 Isolated USB Digital I/O Modules
  • Adlink Technology 51-37111-0C1 cPCI-R8217 cPCI-R3700A PCB Interface Card
  • ADLINK DPAC-3020-11(G) Embedded PC Automation Controller
  • ADLINK NuPRO-840 PICMG 1.0 industrial Single Board
  • Adlink 6U CompactPCI 2.0 Blades cPCI-6965
  • ADLINK PCI-9114DG Multi-Function DAQ Card
  • Adlink NuPRO-E43 PICMG Single Board Computers
  • Adlink PCI-7856 Distributed Motion Control
  • ADLINK Mini-ITX Embedded Boards MI-965
  • ADLINK NuPRO-E340 industrial control motherboard
  • ADLINK NuPRO-595 Series Full-Size PICMG 1.0 SBC
  • ADLINK PCIe-GIE64+ / PCIe-GIE62+ 4 / 2-CH PCI Express® Power over Ethernet Frame Grabbers
  • ADLINK CPCI-6910AM-M1G 6U Dual Core Xeon CompactPCI Universal SBC
  • ADLINK/AMPRO CM-435-v2/CM-435 Extreme Rugged™ PC/104 Single Board Computer
  • ADLINK Technology 51-37111-0C1 PCB Interface Card
  • Adlink Centralized Motion Controllers PCI-8164
  • ADLINK PCI-7230/33/34 32-CH Isolated DIO PCI Cardsrd
  • ADLINK NUPRO-E320DV/NUPRO-E320 industrial control motherboard
  • Adlink PCI-8154 Advanced 4-axis Servo & Stepper Motion Controller
  • Adlink cPCI-3534/3538-S Series 4/8-port Asynchronous Serial Communications Modules
  • ADLINK Adlink Digital I/O PCI-7396
  • ADLINK 6U Rear Transition Modules cPCI-R6700 Series
  • ADLINK cPCI-6700B Industrial Control Board
  • ADLINK NuPRO-965/ NuPRO-965LV PICMG Single Board Computers
  • ADLINK HSL-DI16DO16-M-NN 16-CH Discrete Input 16-CH Discrete Output Module
  • Adlink cPCI-6770 6U CompactPCI 2.0 Blades
  • ADLINK NuPRO-598 REV A1 INDUSTRIAL CONTROL MOTHERBOARD
  • ADLINK PCI-7200 PCI Motion Control Card Acquisition Card 51-12001-0C20
  • ADLINK TECHNOLOGY EOS-1200/M4G/SSD32G(G) Industrial Systems
  • ADLINK Centralized Motion Controllers PCI-8134
  • ADLINK cPCI-HR6847E/M2G-1 COMPACT PCI BOARD
  • ADLINK PXIE-8638 BUS EXPANSION MODULE
  • ADLINK cPCI-6910 6U CompactPCI 2.0 Blades
  • Adlink NuPRO-E42 51-41808-0A30 Industrial Motherboard
  • ADLINK IH61-AA400-A4A1E (IMB-M40H) Industrial Motherboard
  • ADLINK PCIe-GIE64+ GigE Vision Frame Grabber Card
  • ADLINK MXC-6322D(G) Industrial Fanless Computer working
  • ADLINK CPCI-7300 32-CH 80 MB/s High-Speed Digital I/O Module
  • Adlink cPCI-8168 Advanced 6U Compact PCI 8-Axis Motion Controller
  • Adlink VME CPU Board cPCI-6626/2710/M4G
  • ADLINK  cPCI-R6200 high-performance 6U CompactPCI Rear Transition Module (RTM)
  • Adlink cPCI-7248 48-CH Opto-22 Compatible Digital I/O Module
  • ADLINK DLAP-211-JNX/DLAP-211-JT2/ DLAP-211-Nan
  • ADLINK cPCI-3544 4-Port RS-422/485 Isolated Serial Communications Card
  • Hirschmann MSP30-16040SCZ999HHE2A Manage the basic unit of the industrial DIN-Rail switch
  • Hirschmann MSP30-16040SCY999HHE2A
  • Hirschmann RS20-0400S2S2SDAEHC09.0.00 Management-type industrial fast Ethernet switch
  • Hirschmann Belden OCTOPUS OS20-002800T5T5T5-TBBY999GMSE3S Manageable industrial Ethernet switch
  • HIRSCHMANN OS20-000800T5T5T5-TBBU999H5SE2S
  • HIRSCHMANN RS20-0800M4M4SDAEHC09.0.14 industrial switch
  • Hirschmann RS20-0800T1T1SDAUHC RS20-0800T1T1SDAE
  • Hirschmann MSM20-M2M2M2M2SY9HH9E99.9 Fast Ethernet Media Module
  • HIRSCHMANN RS30-1602T1T1SDAEHC09.0.10 industrial switch
  • HIRSCHMANN MAR1040-4C4C4C4C9999SMMHPHH Managed Etherne