Field Device Systems Integrator (FDSI) modules
Intrinsically Safe I/O Subsystem (ISCM)
DCS Fieldbus Modules for Siemens APACS+™
Systems
DCS Fieldbus Modules for Westinghouse
WDPF® Systems.
DCS Fieldbus Modules for Fisher's PROVOX®
Series 20 Migration with HART.
DCS Fieldbus Modules for Honeywell® TDC
2000 Systems with HART.
The ZCP270 with FCM100Es supports the following
devices on the 268 Kbps Fieldbus:
100series FBMs (FBM01. FBM02. and so forth)
Fieldbus Cluster I/O via FBP10 Fieldbus
processor module
Foxboro® Hydrostatic Interface Unit (HIU)(1)
Foxboro Mass Flowmeter
Foxboro Panel Display Stations
SPECTRUM™ Migration Integrators
SPEC 200™ Control Integrators
SPEC 200 MICRO™ Control Integrators
SPEC 200 CCM Control Integrators
DCS Fieldbus Modules for Honeywell® TDC 2000
and TDC 3000 systems
DCS Fieldbus Modules for Bailey® Net90 and
Infi90 systems
DCS Fieldbus Modules for Fisher’s PROVOX®
Series 10. Series 20 and Controller Series
systems.
MOUNTING STRUCTURE
The ZCP270 are installed in the 1x8 and 2x8
mounting structures. The two modules of a fault
tolerant ZCP270 must be mounted in adjacent
mounting structure slots to allow for installation of the
interconnecting fault-tolerant connector
LED INDICATORS
Light-emitting diodes (LEDs) on the front of the
ZCP270 module provide visual indication of the:
ZCP270 operational status
Communications activity of Ethernet control
network A and B links
Communications activity of Ethernet fieldbus A
and B.
The control network path Tx LEDs indicate which
controller is primary as well as the network path it is
using; these LEDs are only active on the primary
module
FUNCTIONAL SPECIFICATIONS
Processor Type
CONTROL PROCESSOR
Microprocessor-based AMD Elan SC520 (running
at 100 MHz) with stored programs, using high
speed communication capability.
Memory (per processor)
SIZE
16 MB SDRAM
32 MB flash memory
ERROR DETECTION
ECC providing single-bit error detection and
correction as well as multiple-bit error detection.
Process I/O Communications (with FCMs)
100 MBPS FAST ETHERNET
Transmission Rate
100 Mbps to the FCM100Et or FCM100E
Cable Lengths
ZCP270. FCM100Et or FCM100E TO
ETHERNET SWITCH
2 km (1.24 mi) maximum
Process I/O Capacity
WITH FCM100Et
FCM100Et Modules
32 (maximum) per ZCP270 Ethernet trunk
fieldbus
200 Series FBMs
128 (maximum) Fieldbus Modules depending
on the number of FCM100Ets implemented
and control processor sizing constraints
(refer to ZCP270 Sizing Guidelines
[B0700AW]).
WITH FCM100E
FCM100E Modules
32 (maximum) per ZCP270 Ethernet trunk
fieldbus
200 Series FBMs
128 (maximum) Fieldbus Modules depending
on the number of FCM100Es implemented
and control processor sizing constraints
(refer to ZCP270 Sizing Guidelines
[B0700AW]).
WITH FCM100E (CONT.)
100 Series FBMs
64 (maximum) per ZCP270 Ethernet trunk
128 (maximum) Fieldbus Modules depending
on the number of FCM100Es implemented
and control processor sizing constraints
(refer to ZCP270 Sizing Guidelines
[B0700AW]).
Maximum Number of Blocks Configured
The maximum number of blocks that can be
configured for the ZCP270 (or fault-tolerant ZCP270
pair) is 4000.
Memory Allocation for Blocks
5.8 MB
Block Executions Per Second
10.000 blocks/second, maximum
Maximum Blocks Processed
The number of blocks that can be processed per
basic processing cycle (BPC) time interval depends
on control processor sizing constraints and block
type selection. These blocks include all types (control
blocks, ECBs, compounds, data blocks, and so
forth). For sizing guidelines, refer to ZCP270 Sizing
Guidelines (B0700AW).
Minimum Block Processing Cycle (BPC)
50 ms
Sequence Block Size
32 KB maximum for each block
Maximum Number of IPC Connections
131; 100 connections for source points; 30
connections for sink points; 1 connection for internal
use only.
30 IPC connections
100 IPC connections
ZCP270
Maximum Number of OM Sink Lists
50
Maximum OM Scanner Database
12.000 points for BPC ≥ 200 ms
5.000 points for BPC ≤ 100 ms
FUNCTIONAL SPECIFICATIONS (CONTINUED)
Maximum Number of OM Sink Points
7.500
Configurable Block Periods
0.05. 0.1. 0.2. 0.5. 0.6. 1. 2. 5. 6. 10. 30 seconds
1. 10. 60 minutes
Basic Processing Cycle
0.05. 0.1. 0.2. 0.5. and 1.0 seconds, selectable at
system configuration time
Time to Marry Fault-Tolerant Modules
<1s
Internal Diagnostics
Self-checking performed at power-up. Run-time
checks and the watchdog timer function performed
during operation.
Infrared Communications
Letterbug assignment via the Letterbug Configurator.
Letterbug or Hardware ID readout via the Letterbug
Configurator.
Power Requirements
INPUT VOLTAGE (REDUNDANT VOLTAGE)
39 V dc typical
CONSUMPTION (PER NON-FAULT-TOLERANT
MODULE)
15 W, maximum
Regulatory Compliance
CE CERTIFICATION
For the ZCP270 to meet CE certifications
required in European installations, shielded
enclosures are required as described in Power,
Earthing (Grounding), EMC and CE Compliance
(B0700AU).
ELECTROMAGNETIC COMPATIBILITY (EMC)
European EMC Directive 89/336/EEC
Meets: EN 50081-2 Emission standard
EN 50082-2 Immunity standard
EN 61326 Annex A for Industrial
Environments
Regulatory Compliance (Continued)
CISPR 11. Industrial Scientific and Medical
(ISM) Radio-frequency Equipment -
Electromagnetic Disturbance Characteristics - Limits and Methods of Measurement