le plus faible) peut être utilisé pour déterminer le
code de température global du système. Les
combinaisons d’équipements dans le système sont
sujettes à inspection par les autorités locales
qualifiées au moment de l’installation.
EXPLOSION HAZARD -
• Do not disconnect equipment unless
power has been removed or the area
is known to be nonhazardous.
• Do not disconnect connections to
this equipment unless power has
been removed or the area is known
to be nonhazardous. Secure any
external connections that mate to
this equipment by using screws,
sliding latches, threaded
connectors, or other means provided
with this product.
• Substitution of components may
impair suitability for Class I, Division
2.
• If this product contains batteries,
they must only be changed in an
area known to be nonhazardous.
RISQUE D’EXPLOSION –
• Couper le courant ou s’assurer que
l’environnement est classé non
dangereux avant de débrancher
l'équipement.
• Couper le courant ou s'assurer que
l’environnement est classé non
dangereux avant de débrancher les
connecteurs. Fixer tous les connecteurs
externes reliés à cet équipement à
l'aide de vis, loquets coulissants,
connecteurs filetés ou autres moyens
fournis avec ce produit.
• La substitution de composants peut
rendre cet équipement inadapté à une
utilisation en environnement de Classe
1, Division 2.
• S’assurer que l’environnement est
classé non dangereux avant de changer
les piles.
Specifications
Adapter Specifications
Expansion I/O Capacity Maximum of 63 modules
Maximum of 5 Rack Optimized connections (for digital modules
only)
Maximum of 20 direct connections
1734-AENT backplane current output = 1.0A.
The actual number of modules can vary. Add up the current
requirements of the modules you want to use to make sure they do
not exceed the amperage limit of 1.0A for the 1734-AENT.
Backplane current can be extended beyond 1.0A by using
1734-EP24DC backplane extension Power Supplies. Add multiple
1734-EP24DC modules to reach the 63 module maximum).
Cat. No. PointBus Current Requirements
1734-IB2 75mA
1734-IB4 75mA
1734-IB8 75mA
1734-IV2 75mA
1734-IV4 75mA
1734-OB2 75mA
1734-OB4 75mA
1734-OB8 75mA
1734-OB2E 75mA
1734-OB2EP 75mA
1734-OB4E 75mA
1734-OB8E 75mA
1734-OV2E 75mA
1734-OV4E 75mA
1734-OW2 80mA
1734-OX2 100mA
1734-IE2C 75mA
1734-OE2C 75mA
1734-IE2V 75mA
1734-OE2V 75mA
1734-IA2 75mA
1734-IM2 75mA
1734-OA2 75mA
1734-IJ2 160mA
1734-IK2 160mA
1734-IR2 220mA
1734-IT2I 175mA
1734-SSI 110mA
1734-VHSC5 180mA
1734-VHSC24 180mA
1734-232ASC 75mA
1734-485ASC 75mA
EtherNet
Communication Rate
10/100Mbits/s, half or full-duplex
Module Location Starter module - left side of the 1734 system
Power Supply Specifications
Input Voltage Rating 24V dc nominal
10-28.8V dc range
Field Side Power
Requirements
24V dc (+20% = 28.8V dc maximum) @ 400mA maximum
Inrush Current 6A maximum for 10ms
Interruption Output voltage will stay within specifications when input drops out
for 10ms at 10V with maximum load.
General Specifications
Indicators 4 red/green status indicators
Adapter status
PointBus status
Network activity status
Network status
2 green power supply status indicators:
System Power (PointBus 5V power)
Field Power (24V from field supply)
Power Consumption 4.5W maximum @ 28.8V dc
Power Dissipation 15.5W maximum @ 28.8V
PointBus Output
Current
1A maximum @ 5V dc ±5% (4.75 - 5.25)
Input Overvoltage
Protection
Reverse polarity protected
Thermal Dissipation 9.5 BTU/hr maximum @ 28.8V dc
Isolation Voltage Tested to withstand 1800V dc for 60s
Field Power Bus
Nominal Voltage
Supply Voltage Range
Supply Current
24V dc
10-28.8V dc range
10A maximum
Dimensions Inches
(Millimeters)
3.0H x 2.16W x 5.25L
(76.2H x 54.9W x 133.4L)
Environmental
Conditions
Operational
Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20 to 55° C (-4 to 131° F)
Storage
Temperature
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal
Shock): -40 to 85° C (-40 to 185° F)
Relative Humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat): 5
to 95% noncondensing
Shock IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Operating 30g peak acceleration
Nonoperating 50g peak acceleration
Vibration IEC 60068-2-6 (Test Fc, Operating)
Tested 5g @ 10-500Hz
ESD Immunity IEC 61000-4-2:
6kV contact discharges
8kV air discharges
Radiated RF
Immunity
IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz
10V/m with 200Hz 50% pulse 100%AM from 900MHz
EFT/B Immunity IEC 61000-4-4:
+4kV at 5.0kHz on power ports
+2kV at 5.0kHz on communications ports
Surge Transient
Immunity
IEC 61000-4-5:
+1kV line-line(DM) and +2kV line-earth(CM) on communications
ports
+1kV line-line(DM) and +2kV line-earth(CM) on power ports
Conducted RF
Immunity
IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz