Hydran 201Ti Mark IV Essential DGA monitoring for transformers
Hydran 201Ti
Mark IV Essential DGA monitoring for transformers
The HydranTM 201Ti is a small and easy to setup continuous Dissolved Gas-in-oil Analysis (DGA) monitor.
It provides the basic information used by IEEE® Standard C57.104 and can be used as an essential first
line of defence for the transformers in your fleet to obtain advance warning of a failure condition and
minimize the risk of unplanned outages.
The 201Ti’s composite-gas sensor provides the world renown “Hydran gas value” using fuel cell
technology (described as fixed instruments - method 3 in the standard). It responds 100% to Hydrogen
(general fault gas) and is also sensitive to Carbon Monoxide (overheated paper), Acetylene (arcing) and
Ethylene (overheated oil), thus covering all the main transformer failure root causes.
Because the monitoring unit mounts on a single valve and uses Dynamic Oil Sampling, there is no
need for a pump or extra piping to connect to different valves. Due to its uncomplicated features and
the easily understood information it provides, the 201Ti has been amongst the monitors of choice for
many years, with one of the largest installed base of any monitor.
With the latest Mark IV version, the Hydran 201Ti monitor has been completely overhauled with new
electronic boards and power supply to make it RoHS compliant, address any obsolescence issue and
further improve this time proven product.

It now offers additional features like:
• Improved sensor
• Modbus® protocol communication over isolated RS-485
• Local USB port to replace the RS-232 port no longer found on most field laptops
• Compatibility with GE’s acclaimed PerceptionTM Fleet software to download, trend and analyse data,
like with any other GE DGA monitoring equipment
Key Benefits
• Continually measures main H₂ fault gas
• Local LCD display
• Communicates gas ppm value remotely
• Proven and continuously improved design (over 30.000 units sold)
• Easy to install, single valve mount
Easy Asset Supervision
• Permanently mounts on a single transformer
oil valve. No extra piping or pump required
• Gas sensor responds 100% to Hydrogen
(general fault gas) and is also sensitive to
Carbon Monoxide (overheated paper)
• Optional 5 year sensor guarantee
Configurable Alarms
• An alarm is raised when an abnormal level of
fault gas is detected
• Two alarm levels (one for Alert and one for
Alarm) can be set to show increasing severity
• Alarms can be set on gas ppm levels or on gas
rate of change (ROC) over an hour or a day
• Automatic self-test every 15 days will trigger
service alarm if it detects a fault, including
power failure, oil valve closed, sensor or
battery needing replacement
Communication
• Local LCD display of the real-time dissolved
gas ppm value
• Analogue output (4-20mA) of the dissolved
gas ppm value
• Digital output of registers using Modbus or
Hydran protocols over isolated RS-485
• 3 dry contact relays also available 2 for the
fault gas alarms and one for the service alarm
Controllers
Remote PC
The 201Ti can be connected to optional controllers to facilitate communication
with multiple units and create a local network.
• The Ci-1 controller is a one channel controller that replicates some of the human
interface functions (gas value display, alarm buttons). This is ideal when the
201Ti is mounted out of reach on an upper valve of the transformer. It also
brings down the alarm relay contacts and the analogue output for easier wiring.
• The Ci-C controller receives the gas ppm data from up to four H201Ti, providing
a single communication point for all four monitors. It has no alarm relay or
analogue output. This is ideal when protecting 3 single phase transformers + 1
spare.
It is possible to “daisy-chain” up to 32 controllers or 201Ti through their RS-485
port. The maximum chain distance (all cables added up) is 1200m (4000ft). All the
201Ti connected to any of the daisy-chained controllers can be accessed through
any controller in the local network, thus facilitating communication by only having
to fit one RS-232 modem for example.
Technical Specifications
MEASUREMENTS
Sensor
• Fuel cell type sensor behind a gas-permeable
membrane in contact with mineral transformer
insulating oil through a flooded manifold
• Measurement range 0-2000 ppm (volume/ volume,
H₂ equivalent)
• Measurement accuracy ± 10 % of reading ± 25
ppm (H₂ equivalent)
Relative Sensitivty
• H₂: 100 % of concentration
• CO: 15 ± 4 % of concentration
• C₂H₂: 8 ± 2 % of concentration
• C₂H₄: 1.5 ± 0.5 % of concentration
Relative Sensitivty
• 10 minutes (90% of step change)
FEATURES
Display
• Backlit LCD, 2 lines x16 characters
• Keypad to setup unit and acknowledge alarms
Digital Communications
• USB port (type B connector) for local connection to
laptop computer for configuring the system
• RS-485 (terminal block), isolated to 2000 Vac
RMS, for supervisory link connection to optional
controllers and for remote communication
• Gas level (ppm) and gas rate of change (hourly
or daily ppm) outputs using Modbus or Hydran
Protocols over RS-485
Analouge Communications
• Gas level ppm output using 4-20mA for 0-2000
ppm range, 10V load maximum, isolated to 2000
Vac RMS
Alarms
• 3 different alarms: Gas Alert (Hi), Gas Alarm (HiHi)
and Service Alarm (battery, sensor, temp)
• Gas alarms can be set on gas level reached or on
hourly or daily trend (gas level rate of change)
• 3 dry contact relays (type C, SPDT), NO/NC,
3A@250Vac resistive load, 3A@30Vdc resistive load
Others
• External sampling port for glass syringe with Luer
stop cock
ENVIRONMENT
Conditions
• Operating ambient temperature -40°C to +55°C
(-40°F to +131°F)
• Operating ambient humidity 0-95% RH,
non-condensing
• Oil temperature at valve -40°C to +105°C (-4°F to
+221°F) with finned heat sink adapter option
• Oil pressure at valve 0-700KPa (0-100psi)
• Vacuum resistant sensor
Digital Energy
Lissue Industrial Estate East
Lissue Road
Lisburn BT28 2RE United Kingdom
Tel: +44 (0) 2892 622915
Enclosure Rating
• NEMA Type 4X certified
• Meets requirements of IP66
Power Requirements
• 90–132 Vac or 180–264 Vac switchable, 47–63 Hz,
475VA max
Mechanical
• Cylindrical shape, diameter 178mm (7”) x length
180mm (7-1/8”)
• Mounts on either 1”, 1.5” or 2” female NPT valve
• Installed weight 5.6Kg (12lb)
• Shipping weight 6.9Kg (15lb)
OPTIONS
• Adapters for non NPT valves
• Finned heat sink adapter (1.5”), for use when
ambient temperature is above 40°C (104°F) or oil
temperature is above 90°C (194°F)
• Special tube wrench for sensor installation and
removal
• H201Ci-1 one-channel controller
• H201Ci-C four-channel controller
• Accessories/options for controllers

| User name | Member Level | Quantity | Specification | Purchase Date |
|---|