Foxboro FBM02 FBM04 Thermocouple/mV Input Module
FBM202 Thermocouple/mV Input Module
he FBM202 Thermocouple/mV Input contains eight thermocouple input channels, and one isolated RTD
reference junction compensation channel.
OVERVIEW
The FBM202 Thermocouple/mV Input contains eight
thermocouple input channels, and one isolated RTD
reference junction compensation channel (for terminal
temperature sensing). Each thermocouple/mV
channel accepts standard thermocouples for various
temperature ranges, and each provides
thermocouple burnout detection (up-scale). The
inputs are galvanically isolated from other channels
and ground.
The module performs the signal conversion required
to interface the electrical input signals from the field
sensors to the optionally redundant Fieldbus. It
executes an Analog Input application program, which
provides integration time and Rate of Change Limits
configurable options
When connected to the appropriate TAs, the
FBM202 module provides functionality formerly
provided by the 100 Series FBM I/O subsystem. TAs
are available which support the functionality of the
100 Series FBM02.
FEATURES
Key features of the FBM202 are:
Eight channels for input of thermocouple signals
One isolated RTD reference junction
compensation channel (for terminal temperature
sensing)
Each input channel is galvanically isolated
Rugged design suitable for enclosure in Class G3
(harsh) environments
Execution of an analog input application program
that provides conversion time and configurable
options for Rate of Change Limits
High accuracy achieved by sigma-delta data
conversions for each channel
Termination Assemblies (TAs) for locally or
remotely connecting field wiring to the FBM202
HIGH ACCURACY
For high accuracy, the module incorporates Sigma
Delta data conversion on a per-channel basis, which
can provide new analog input readings every 25 ms,
and a configurable integration period to remove any
process noise and power line frequencies.
Each time period, the FBM converts each analog
input to a digital value, averages these values over
the time period and provides the averaged value to
the controller.